background image

18 - 

User manual

 

If Dip-Switch 2 contacts are opened, the baud rate is selected on parameter 112 

bd.rt.

 (

“Baud Rate”

 word 2112).

Module

 can introduce a delay (in milliseconds) of the response to the master 

request. This delay must be set on parameter 114 

se.de. 

(

“Serial Delay”

 word 2114).

Each parameter modification is saved by the controller in the EEPROM memory 

(100000 writing cycles), while the setpoints are saved with a delay of 10 seconds 

after the last modification. 

NB

: Changes made to words that are different from those reported in the following 

table can lead to malfunction.

Modbus RTU protocol features

Baud-rate

Selectable on par. 112 

bd.rt.

Value 0: 4800bit/s 

Value 4: 38400bit/s

Value 1: 9600bit/s 

Value 5: 57600bit/s

Value 2: 19200bit/s 

Value 6: 115200bit/s

Value 3: 28800bit/s

Format

Selectable on par. 113 

s.p.p.

Value 0: 8N1 

Value 3: 8N2

Value 1: 8E1 

Value 4: 8E2

Value 2: 8O1 

Value 5: 8O2

Supported 

functions

WORD READING (max 20 word) (0x03, 0x04)

SINGLE WORD WRITING (0x06)

MULTIPLE WORDS WRITING (max 20 word) (0x10)

RO = Read Only

R/W = Read/Write

WO = Write Only

Modbus 

address

Descrizione

Read 

Write

Reset 

value

0

Type of device

RO

490

1

Software version

RO

Flash

2

Boot version

RO

Flash

3

Slave address

RO

Eepr/dip

6

Baud rate

RO

Eepr/dip

50

Automatic addressing

WO

-

51

Installation code comparision for automatic 

learning of slave address

WO

-

500

Loading default values (write 9999)

RW

0

501

Restart (write 9999)

RW

0

1000

Process (tenth of degree)

RO

-

1001

Command setpoint (tenth of degree)

R/W

EEPROM

1002

Alarm 1 setpoint (tenth of degree)

R/W

EEPROM

1003

Start/Stop

0=controller in STOP

1=controller in START

R/W

0

Содержание ISO-plus-CAN

Страница 1: ...ISO plus CAN ISO plus RS4 User manual...

Страница 2: ...2 7 6 Synchronized tuning 12 7 7 Automatic Manual regulation for output control 13 7 8 Heater Break Alarm on CT Current Transformer 13 7 9 Dual Action Heating Cooling 14 7 10 Soft Start function 16 7...

Страница 3: ...ualified personnel should be allowed to use the device and or service it and in accordance to technical data and environmental conditions listed in this manual Do not dispose electric tools together w...

Страница 4: ...0 10 V Ri 110 k 0 20 mA Ri 50 4 20 mA Ri 50 0 60 mV Ri 500 k Logic output 2 x SSR Configurable as command or alarm output 24VDC 15 50mA Analogue output 1 x 0 4 20 mA Configurable as command output ala...

Страница 5: ...wing safety guidelines Separate control line from power wires Avoid proximity of remote control switches electromagnetic contactors powerful engines and use specific filters Avoid proximity of power g...

Страница 6: ...ermo PT NI100 13 14 15 For thermoresistances PT100 Ni100 For the three wire connection use wires with the same section For the two wire connection short circuit terminals 13 and 15 When shielded cable...

Страница 7: ...20 mA with external power supply for sensor Comply with polarity A Sensor output B Sensor ground P 0 100mbar Pmax 3bar T 0 70 C OUT 4 20mA IN 9 33V DC C A PRESSURETRANSMITTER SENSOREDIPRESSIONE 4 20m...

Страница 8: ...status of output OUT1 During test pressing key if the command output is OUT1 blinks with frequency 50ms At the end of current acquisition by the CT blinks with frequency 0 5s if the operation has been...

Страница 9: ...ing default values If contacts 1 3 are OFF modbus baud rate is selected on parameter 112 bd rt If contact 4 is ON parameters and all eeprom datas are loaded with default values default 19 200baud addr...

Страница 10: ...launch the manual tuning when the process is far from setpoint 7 5 AutoTuning Launch Once Set 3 on parameter 31 tune word 2031 Autotuning procedure is executed only once at next ISO plus restart If th...

Страница 11: ...itch off the manual functioning will be maintained as well as the previously set output percentage value If the sensor breaks during automatic functioning the controller moves to manual mode while mai...

Страница 12: ...Alarm selection Cooling p b M word 2042 Proportional band multiplier ou d b word 2043 Overlapping Dead band co c t word 2044 Cooling time cycle Par p b M that ranges from 1 00 to 5 00 determines the p...

Страница 13: ...EAT ALARM OUTPUT COOL SPV PV ACTIVE ACTIVE SPV PV ACTIVE ACTIVE The parameter co c t has the same meaning as the heating time cycle t c Par 41coo F CoolingFluid word2041 pre selectstheproportionalband...

Страница 14: ...ansmission function on analogue output If not used as command the anaolgue output can be used to retransmit process setpoint current read by the C T input output percentage Select on parameter 100 rEt...

Страница 15: ...ternal master Es PLC HMI panel It is possible to configure output status at starting and in case of error programming parameters 122 131 see par 9 Into this mode refer to modbus words 1500 1508 see pa...

Страница 16: ...e 5 57600bit s Value 2 19200bit s Value 6 115200bit s Value 3 28800bit s Format Selectable on par 113 s p p Value 0 8N1 Value 3 8N2 Value 1 8E1 Value 4 8E2 Value 2 8O1 Value 5 8O2 Supported functions...

Страница 17: ...FF 1 ON Bit0 Green led Bit1 Red led OUT1 Bit2 Red led OUT2 RO 0 1008 Alarm status 0 absent 1 present Bit0 Allarme 1 Bit1 Allarme 2 RO 0 1009 Error flags Bit0 Cold junction error Bit1 Process error sen...

Страница 18: ...T2 RO 0 1108 Command output percentage 0 10000 Heating output percentage in doulbe loop R W 0 1200 Process if temperature with tenth RO 1201 Command setpoint if temperature with tenth R W EEPROM 1202...

Страница 19: ...ror in eeprom writing Bit3 Error in eeprom reading Bit4 Error missing calibration Bit5 Generic error Bit6 Hardware error Bit7 Error H B A SSR in short circuit Bit8 Error H B A SSR open charge Bit9 Err...

Страница 20: ...RO 0 1232 Process if temperature no tenth RO 1233 Command setpoint if temperature no tenth R W EEPROM 1234 Alarm 1 Setpoint if temperature no tenth R W EEPROM 1235 Alarm 2 Setpoint if temperature no t...

Страница 21: ...600 C 14 0 10 V 15 0 20 mA 16 4 20 mA 17 0 60 mV 18 Potenziometer set the value on parameter 5 2 deGr Degree Word modbus 2002 0 C Centigrade Default 1 F Fahrenheit 2 K Kelvin 3 Lo L i Lower Linear Inp...

Страница 22: ...alibration Word modbus 2008 Percentage value that is multiplied for the process value allows to calibrated the working point Ex to correct the range from 0 1000 C showing 0 1010 C set the par to 1 0 1...

Страница 23: ...017 Selects controller status at starting 0 Start Default 1 Stop 2 Stored Backs the controller to the Start Stop status existing before the switching off 18 Act t Action type Word modbus 2018 0 Heatin...

Страница 24: ...d Reset Word modbus 2022 Type of reset for state of command contact always automatic in P I D functioning 0 Automatic reset Default 1 Manual reset by word 1029 2 Manual reset stored keeps relay status...

Страница 25: ...onal Band Word modbus 2033 Process inertia in units 0 ON OFF if also t i is equal to 0 Default 1 10000 digit degrees tenths for temperature sensors 34 i t Integral Time Word modbus 2034 Process inerti...

Страница 26: ...15s 41 coo F Cooling Fluid Word modbus 2041 Type of refrigerant fluid for heating cooling PID Enable cooling output on par AL 1 or AL 2 0 Air Default 1 Oil 2 Water 42 P b M Proportional Band Multiplie...

Страница 27: ...ord modbus 2048 Selects the min proportional band value selectable by the automatic tuning 0 10000 digit degrees tenths for temperature sensors Default 50 49 ma p b Maximum Proportional Band Word modb...

Страница 28: ...aching alarm1 3 N C Threshold Normally closed active on reaching alarm1 58 a 1 Hy Alarm 1 Hysteresis Word modbus 2058 10000 10000 digit degrees tenths for temperature sensors Default 0 5 59 a 1 s e Al...

Страница 29: ...up D 9 5 GROUP E ALARM 2 68 AL 2 Alarm 2 Word modbus 2068 The alarm intervention is related to Alarm 2 0 Disabled Default 1 Absolute alarm threshold referred to process active above 2 Absolute alarm t...

Страница 30: ...ontact if alarm 1 on Q1 or Q2 72 a 2 s S Alarm 2 State Stop Word modbus 2072 Contact status for alarm output 2 with controller in STOP 0 0 mA if alarm 1 on AO Open contact if alarm 1 on Q1 or Q2 Defau...

Страница 31: ...tput percentage during Soft start 0 100 Default 50 83 SS tH Soft Start Threshold Word modbus 2083 Threshold under which the device enables percentage soft start function at starting 10000 10000 digit...

Страница 32: ...200 Ampere Default 50 92 H b a t Heater Break Alarm Threshold Word modbus 2092 Heater Break Alarm activation threshold 0 Alarm disabled Default 0 1 200 0 Ampere 93 ocu t Overcurrent Alarm Threshold Wo...

Страница 33: ...2102 Linear output lower limit range value related to 0 4 mA 32767 32767 digit degrees for temperature sensors Default 0 103 up L r Upper Limit Retransmission Word modbus 2103 Linear output upper lim...

Страница 34: ...s the type of format for the modbus RTU communication 0 8 N 1 8 bit no parity 1 stop bit Default 1 8 E 1 8 bit even parity 1 stop bit 2 8 O 1 8 bit odd parity 1 stop bit 3 8 N 2 8 bit no parity 2 stop...

Страница 35: ...ied 1 commute Default 0 124 E vA o Error Value Output Word modbus 2124 Defines values to be assumed by the outputs in case of error or off line Bit 0 Q1 0 off 1 on Default 0 Bit 1 Q2 0 off 1 on Defaul...

Страница 36: ...ut in case of error or off line 32767 32767 digit Default 0 131 C t ou Current Transformer Output Word modbus 2131 Defines digital output connected to the current transfomer 0 Q1 Default 1 Q2 132 136...

Страница 37: ...Par 58 a 1 HY 0 Command setpoint can be modified by RS485 word 1201 10 c Allarme di Banda word 2056 3 Pv Off Off Hysteresis parameter 0 Time Alarm output Band alarm hysteresis value greater than 0 Pa...

Страница 38: ...zione inferiore word 2056 5 Pv Comand Spv Alarm Spv Off Off On On Hysteresis parameter 0 Time Alarm output Alarm Spv Lower deviation alarm value of alarm setpoint greater than 0 and hysteresis value g...

Страница 39: ...of the word 1009 For other signals see table below Cause Whattodo BIT2 Error in E2PROM cell programming Call Assistance BIT0 Cold junction sensor fault or room temperature outside of allowed limits C...

Страница 40: ...mmand State Stop Word modbus 2021 27 22 c re Command Reset Word modbus 2022 27 23 c de Command Delay Word modbus 2023 27 24 vAL t Valve Time Word modbus 2024 27 25 au ma Automatic Manual Word modbus 2...

Страница 41: ...a 2 s e Alarm 2 State Error Word modbus 2071 33 72 a 2 s S Alarm 2 State Stop Word modbus 2072 34 73 a2 re Alarm 2 Reset Word modbus 2073 34 74 a 2 de Alarm 2 Delay Word modbus 2074 34 75 79 Reserved...

Страница 42: ...Expansion Module Word modbus 2121 39 122 i vA o Initial Value Output Word modbus 2122 39 123 E Mo o Error Mode Output Word modbus 2123 39 124 E vA o Error Value Output Word modbus 2124 39 125 A o ty A...

Страница 43: ...232 RevA Software Rev 0716 Read carefully the safety guidelines and programming instructions contained in this manual before using connecting the device...

Отзывы: