20.1 PDU requirements, common
The system is configured to have two separate, AC source circuits to provide fully redundant power. Thus,
each source circuit must be able to provide the full power to the system. Typically, each source is provided
to a single socket wired into one of the customer's AC circuits. However, certain customers may have
power configurations that will not provide the required amount of power in a single connection. For
example, there could be a lower power single phase PDU where one PDU cannot provide enough power
for the ActiveScale X100 system. For these power configurations, up to two power connections will be
used for each “source” of the system.
Table 20
-
26. Input cord
Length:
3-meter length minimum
Table 20
-
27. Delivered power
Estimated, nominal long term:
7kW
Estimated, max short term (<= 1 hour):
8.3kW
Table 20
-
28. Output frequency
Nominal:
50Hz or 60Hz
Operating range:
47-63Hz
Table 20
-
29. Output connectors (outlets)
Compliant to:
IEC 60320
Type:
C13 (preferred) or C19 (All cables provided are C13 to
C14)
Quantity:
18 (may vary depending on configuration)
Locking:
Locking connector preferred
Connector locking spec
5lbs force retention
Table 20
-
30. Recommended branch circuit protection
Protection device:
Manually resettable circuit breaker.
Protection compliance:
UL489
Protection temperature characteristics:
Protection device trip current should be stable over
operating temperature, such as the behavior of a
hydraulic magnetic circuit breaker.
Short circuit protection (line-to-line, if available):
The PDU should be able to withstand a line-to-line short-
circuit at the end of a 1.8M, 16AWG, C13 cord plugged
into on one of its output connectors without damage to
the PDU or any smoke being emitted.
Short circuit protection (line-to-neutral, if available):
The PDU should be able to withstand a line-to-line short-
circuit at the end of a 1.8M, 16AWG, C13 cord plugged
into on one of its output connectors without damage to
the PDU or any smoke being emitted.
Содержание ActiveScale X100
Страница 1: ...ActiveScale X100 Rackless Instalation Guide 6 68841 03 Rev A with ActiveScale OS 6 0 2 software...
Страница 28: ...ActiveScale OS X100 Rackless Installation Guide 28...
Страница 34: ...ActiveScale OS X100 Rackless Installation Guide 34...
Страница 36: ...ActiveScale OS X100 Rackless Installation Guide 36 Assemble the remaining Storage Enclosure Basics on page 66...
Страница 59: ...ActiveScale OS X100 Rackless Installation Guide 59 Figure 3 14 Installing the I O module...
Страница 68: ...ActiveScale OS X100 Rackless Installation Guide 68...
Страница 76: ...ActiveScale OS X100 Rackless Installation Guide 76...
Страница 80: ...ActiveScale OS X100 Rackless Installation Guide 80 Figure 5 30 Rail attaching to front vertical rail...
Страница 91: ...ActiveScale OS X100 Rackless Installation Guide 91 Figure 6 36 Cabling Storage Node 4...
Страница 92: ...ActiveScale OS X100 Rackless Installation Guide 92 Figure 6 37 Cabling Storage Node 5...
Страница 94: ...ActiveScale OS X100 Rackless Installation Guide 94 Figure 6 39 Cabling System Node 1...
Страница 95: ...ActiveScale OS X100 Rackless Installation Guide 95 Figure 6 40 Cabling System Node 2...
Страница 98: ...ActiveScale OS X100 Rackless Installation Guide 98...
Страница 108: ...ActiveScale OS X100 Rackless Installation Guide 108...
Страница 110: ...ActiveScale OS X100 Rackless Installation Guide 110...
Страница 127: ...ActiveScale OS X100 Rackless Installation Guide 127 Figure 10 19 Post Login Storage Policy...
Страница 155: ...ActiveScale OS X100 Rackless Installation Guide 155 Figure 10 47 Post Login Durability Policy...
Страница 162: ...ActiveScale OS X100 Rackless Installation Guide 162...
Страница 234: ...ActiveScale OS X100 Rackless Installation Guide 234...
Страница 238: ...ActiveScale OS X100 Rackless Installation Guide 238...
Страница 240: ...ActiveScale OS X100 Rackless Installation Guide 240...
Страница 244: ...ActiveScale OS X100 Rackless Installation Guide 244...
Страница 260: ...ActiveScale OS X100 Rackless Installation Guide 260...
Страница 262: ...ActiveScale OS X100 Rackless Installation Guide 262 Figure 21 20 Components and port identification...
Страница 263: ...ActiveScale OS X100 Rackless Installation Guide 263 Figure 21 21 ActiveScale X100 cable wiring key...
Страница 264: ...ActiveScale OS X100 Rackless Installation Guide 264...