Parker EME
Setting up Compax3
192-120103 N13 C3I20T11 / C3I32T11 December 2010
139
4.1.11.
I/O Assignment
For intra-device inputs I0 .. I3 as well as the outputs O0 ... O3 you can choose
between fixed or free assignment (see below).
Control via Profibus does not require an M option (M10 / M12).
If an M option is available, 12 inputs/outputs (ports) are freely assignable. These
can be configured as inputs or outputs by groups of four and be activated resp.
read via Object 121.2 and Object 133.3.
The signal inputs I4 ... I7 are fixedly assigned
If the respective functions are not needed, these inputs can also be used for
control.
I5 and I6 can, for example, be used as free inputs if the limit switch function is
deactivated.
Assignment of the intra-device inputs and outputs
Pin
X12
Input/output
High density/Sub D
1
O
+24 V DC output (max. 400mA)
2
O0
No Error
Only for "fixed
assignment"
Functions are
available, if "Fixed
assignment" was
selected for the I/O
assignment in the
configuration wizard
3
O1
Position / speed / gear synchronization
attained (max. 100 mA)
4
O2
Power stage without current (max.)
100 mA)
5
O3
Axis energized with a setpoint of 0
(max. 100 mA)
6
I0="1":
Quit (positive edge) / Axis enable
I0="0"
Axis disable with delay
7
I1
no Stop
8
I2
JOG +
9
I3
JOG -
10
I4
Reg input
11
I
24V input for the digital outputs Pins 2 to 5
12
I5
Limit switch 1
13
I6
Limit switch 2
14
I7
Machine zero initiator
15
O
GND24V
All inputs and outputs have 24V level.
Maximum capacitive loading of the outputs: 30nF (max. 2 Compax3 inputs can be
connected)
Input-/Output extension
The display of the digital inputs in the optimization window of the C3 ServoManager
does not correspond to the physical status (24Volt=on, 0Volt=off) but to the logic
status: if the function of an input or output is inverted (e.g. limit switch, negatively
switching), the corresponding display (LED symbol in the optimization window) is
OFF with 24Volts at the input and ON with 0 Volts at the input.
Optimization
window display