65
Component Names and Functions
Section 2-1
2.
The shell is connected to the ground terminal (GR) of the Power Supply
Unit inside of the Serial Communications Board. Therefore, the cable
shield can be grounded by grounding the GR of the Power Supply Unit.
3.
With SDA/B or RDA/B, the signal polarity may be reversed by the remote
device. Be sure to check the polarity before wiring.
Applicable Connectors
Plug:
XM2A-0901 (OMRON) or equivalent
Hood:
XM2S-0911-E (OMRON) or equivalent
One plug and one hood are provided for each port.
Recommended Cables
CO-HC-ESV-3P
×
7/0.2 (manufactured by Hirakawa Hewtech Corp.)
Cable length: 500 m max. (The total combined cable length is 500 m max. T-
branch lines must be a maximum of 10 m long.)
Terminating Resistance
Switch: TERM
The terminating resistance switch is provided on the CS1W-SCB41-V1 only.
When an RS-422/485 port is used, set the switch to ON if the Serial Commu-
nications Board is on the end of the transmission line. Refer to
Section 3
Installation and Wiring
for the ON/OFF settings.
Note
The status of terminating resistance setting can be monitored in the words
allocated in the CIO Area. For details, refer to
2-3 I/O Memory Allocations
.
2-Wire or 4-Wire Switch:
WIRE
The 2-wire or 4-wire switch is provided on the CS1W-SCB41-V1 only.
When an RS-422/485 port is used, set the switch to “2” when 2-wire connec-
tions are used, and set the switch to “4” when 4-wire connections are used.
For details, refer to
Section 3 Installation and Wiring
.
External Dimensions
Label
Name
Settings
Factory setting
TERM
Terminating
resistance switch
ON: Terminating
resistance ON
OFF: Terminating
resistance OFF
OFF: Terminating
resistance OFF
Label
Name
Settings
Factory setting
WIRE
2-wire or 4-wire
switch
2: 2-wire
4: 4-wire
2: 2-wire
CS1W-SCB21-V1
CS1W-SCB41-V1
Mounted in the CPU Unit
SCB21-V1
SCB41-V1
130
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...