320
Troubleshooting
Section 11-3
Error conditions
Cause
Remedy
Board/Unit
status
Serial com-
munica-
tions mode
Indicator
display
FINS end
code sent to
FINS trans-
mission
source
Words allo-
cated in CIO
Area
The Board/
Unit con-
verted the
received (via
CPU bus)
FINS com-
mand, but
could not
send the
command to
the remote
device after
conversion.
Serial com-
munications
mode is set
to protocol
macro mode
The SD
@
and
COM
@
indi-
cators do not
flash at all.
0204 hex
(remote node
busy)
Bit 05 of CIO
word n+9/
n+19 (Serial
Gateway
Send Start
Timeout/
Response
Timeout
Flag) is ON.
A Serial
Gateway
send start
timeout has
occurred.
(The con-
verted com-
mand will be
discarded
without being
sent).
The FINS
command
was received
by the Board/
Unit, but the
step transi-
tion in the
communica-
tions
sequence of
the protocol
macro is sus-
pended for
either of the
following rea-
sons.
1) The next
step is a
RECEIVE
command.
2) The WAIT
command is
being exe-
cuted.
Correct the communications
sequence.
Alternatively, include retry
processing at the FINS com-
mand transmission source
for when the FINS response
code 0204 hex is received.
Adjust the time set for the
serial gateway Send Start
Timeout Monitoring Time in
DM Area word m+7/m+17,
as required.
2607 hex
(transmis-
sion com-
mand error
(no right to
execute ser-
vice))
Bit 08 of CIO
word n+9/
n+19 (Serial
Gateway Pro-
hibited Flag)
is ON (pro-
hibited sta-
tus)
The Serial
Gateway is
prohibited.
Turn OFF bits 04/12 of CIO
word n (Port 1/2 Serial Gate-
way Prohibit Switch).
0205 hex
(response
timeout), etc.
Bit 15 of CIO
word m+3/
m+13 (CTS
control) is ON
but bit 4 of
CIO word
n+7/n+17 is
OFF.
CTS control
is set to ON
but the RS
signal from
the remote
device has
not been
input to the
CS signal of
the local
node.
Perform either of the follow-
ing:
Loop the RS-CS signals of
the local node.
Disable CTS control.
Input the RS signal from the
remote node to the CS sig-
nal of the local node and use
CTS control.
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...