32
Specifications
Section 1-6
Converted format
• CompoWay/F commands
• Modbus-RTU commands
• Modbus-ASCII commands
• Host Link FINS commands
Enabled serial com-
munications mode
Serial Gateway mode or protocol macro mode
Queuing functions
Up to five FINS commands can be converted and then queued
for processing.
Protocol macro exe-
cution processing
When a FINS command is received during protocol macro
execution, the Serial Gateway is executed using an interrupt
between steps in the communications sequence. If the next
step is a RECEIVE command, the Serial Gateway will not be
executed until the next step. For other conditions, the interrupt
is executed immediately.
Note
The reception buffer is cleared during Serial Gateway
execution.
Note
The Serial Gateway can be prohibited in protocol macro
mode by turning ON the Serial Gateway Prohibit Switch
in the CIO Area.
Response timeout
monitoring
The time is monitored from when the message is converted
into the specified protocol using the Serial Gateway until the
response is received (in Serial Gateway mode or protocol
macro mode).
Default: 5 s (setting range: 0.1 to 25.5 s)
Note
When a timeout occurs, the FINS end code (0205 hex:
Response timeout) is returned to the source of the FINS
command and a response is received after a timeout
occurs.
Send start timeout
monitoring
The time is monitored from when the FINS command is
received until it is converted into the specified protocol and
starts to be sent (in protocol macro mode only).
Default: 5 s (setting range: 0.1 to 25.5 s)
Note
When a timeout occurs, the FINS end code (0204 hex:
Remote node busy) is returned to the source of the
FINS command. The send processing will not be exe-
cuted and the received FINS command will be dis-
carded.
Send delay
The time can be set from when the message is converted into
another protocol using Serial Gateway conversion until the
data is actually sent. (Serial Gateway or protocol macro mode)
Default: 0 s (setting range: 0.01 to 300.00 s)
Item
Description
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...