244
Communications Frames
Section 6-8
Response Frame
[CMND
S
D
C]
Command Details
Response
Number of write data registers
(e.g, 1 register)
0001
hex
Set 0001 hex in controller data s+3 of
CMND(490).
Number of attached data registers
Note: Set 02 hex of this value in
the leftmost byte of S+4. Set 00
hex as the leftmost register No. in
the rightmost byte of S+4.
0200
hex
Set 0200 hex in controller data s+4 of
CMND(490).
Register No. 0002 hex data (e.g.,
0064 hex)
Note: Set 64 hex as the rightmost
register No. in the leftmost byte of
S+5.
6400
hex
Set 6400 hex in controller data s+5 of
CMND(490).
Item
Set
value
Setting location
Item
Setting
Setting location
Modbus Slave address (e.g., 02 hex)
02 hex
Stored in D+2 of CMND(490)
FUNCTION code: Write data (= 10 hex)
10 hex
Write data register No. (e.g., frequency reference = 0002 hex)
0002 hex
Stored in D+3 of CMND(490)
Write data registers (e.g., 1 register)
0001 hex
Stored in D+4 of CMND(490)
Operand
Offset
Value
Meaning
S:
D01000
+0:
2804 hex
Conversion to Modbus-RTU (FINS command code: 2804 hex)
+1:
0210 hex
Modbus-RTU slave address: 02 hex, FUNCTION code: 10 hex (DATA WRITE)
+2:
0002 hex
Write data register No.: 0002 hex (frequency reference)
+3:
0001 hex
Number of write data registers: 0001 hex (1 register)
+4:
0200 hex
Number of attached data bytes: 02 hex (2 bytes); Leftmost register No.: 00 hex
+5:
6400 hex
Rightmost register No.: 64 hex (Frequency reference value: 10.0 Hz when unit is 0.1
Hz), blank = 00 hex
D:
D02000
First response storage word
C:
D00000
+0:
00 0C hex
Number of command data bytes: 000C hex (12 bytes decimal)
+1:
00 0A hex
Number of response data bytes: 000A hex (10 bytes decimal)
+2:
0002 hex
Send destination network address: 02 hex; Serial port number: 0 hex (direct serial port
unit address specification)
+3:
058C hex
Send destination node address: 05 hex; Send destination unit address: 8C hex
+4:
0000 hex
Response required; Communications port number: 0; Resends: 0 hex
+5:
0000 hex
Response monitoring time: 2 s
Operand
Offset
Value
Meaning
D:
D02000
+0:
2804 hex
Conversion to Modbus-RTU (FINS command code: 2804 hex)
+1:
0000 hex
FINS end code: 0000 hex (normal)
+2:
0210 hex
Modbus-RTU slave address: 02 hex, FUNCTION code: 10 hex (DATA WRITE)
+3:
0002 hex
Write data register No.: 0002 hex (frequency reference)
+4:
0001 hex
Number of write data registers: 0001 hex (1 register)
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...