Setup Area Allocations
Section 5-2
If user port settings are specified, set bits 00 to 04 and set the baud rate in
D32001.
Setting Example:
0600 Hex = Protocol macro mode with default port settings and baud rate.
Serial Communications
Mode
Set the serial communications mode to 6 Hex to use protocol macros.
Start Bits, Data Length,
Stop Bits, Parity, and
Baud Rate
If user settings are specified for the port settings, the number of start bits, data
length, number of stop bits, parity, and baud rate must be set. The start bits
setting, however, will be ignored and 1 start bit will always be used.
Do not set the baud rate setting to between A and F. A setup error will occur if
these settings are used, and the default setting of 9,600 bps will be used. Do
not use settings 1 and 2, which are reserved for the system.
Serial Gateway Response Timeout Monitoring Time (Unit Ver. 1.2 or Later Only)
The response timeout condition is monitored when a FINS command is con-
verted to the specified protocol and sent.
0: 5 s (default); Setting range: 01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
The response monitoring time is 5 s when set to the default (0), or can be
user-specified in the range 0.1 to 25.5 s by setting between 01 and FF hex.
Serial Gateway Send Start Timeout Monitoring Time (Unit Ver. 1.2 or Later Only)
When converting FINS commands to the specified protocol and sending them
during execution of protocol macros, the timeout condition is monitored from
when the FINS command is received until the command starts to be sent in
the specified protocol.
0: 5 s (default); Setting range: 01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
The response monitoring time is 5 s when set to the default (0), or can be
user-specified in between 0.1 and 25.5 s by setting the time to between 01 to
FF hex.
Transmission Method
Set half-duplex (0) or full-duplex (1) as the transmission mode for the external
device.
Note
Half-duplex: Allows data to be sent between two Units in one direction only at
any one time.
Full-duplex: Allows data to be exchanged both ways between two Units at the
same time.
With half-duplex transmissions, the reception buffer is cleared immediately
before the sequence is executed and immediately following SEND completion
(SEND or SEND&RECV command). Therefore, the data received before and
during SEND execution cannot be accessed as receive data by the next
RECV command.
Note
When using SEND with half-duplex transmission, there is a time lag, t1,
between data send processing completion and SEND completion. Therefore,
if there is a rapid response from the remote device and a response is returned
for SEND after data is sent (communications or other command) and before
SEND is completed, the response during that time cannot be received using
half-duplex transmissions. If this problem occurs, use the full-duplex transmis-
sions.
or
A
B
A
B
A
B
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...