246
Communications Frames
Section 6-8
• Host Link FINS Settings
Command Frame
Response Frame
[CMND
S
D
C]
Command Details
Response
Note
1.
The method used to set the remote destination network address, node ad-
dress, and unit address for sending data to or receiving data from the PLC
Serial Communications Unit
unit number
6
Use the following equation to
calculate the unit address of the
serial port.
81 hex + 4 hex
×
unit number 6
= 99 hex (153 decimal)
Use CX-Net to set the local net-
work tables in the routing tables.
Unit number
Network
address
Serial Communications Unit
serial port
Port 2
Serial Commu-
nications Unit’s
serial port unit
address: 153
(decimal)
Serial port net-
work address: 5
(decimal)
Item
Setting
Setting location
FINS command code (e.g., change
operating mode (stop operation))
0402 hex
Set in 0402 hex of control
data S for CMND(490)
instruction
FINS command parameter (e.g.,
always FFFF hex to change operating
mode)
FFFF hex
Set in FFFF hex of control
data s+1 for CMND(490)
instruction
Item
Setting
Setting location
FINS command code (E.g., change
operating mode (stop operation))
0402 hex
Stored in D of CMND(490)
instruction
FINS command end code (normal end:
0000 hex)
0000 hex
Stored in D+1 of CMND(490)
instruction
Item
Value (example)
Setting location
Operand
Offset
Value
Meaning
S:
D01000
+0:
0402 hex
Change operating mode (stop operation) (FINS command code: 0402 hex)
+1:
FFFF hex
Change operating mode (stop operation): Always FFFF hex
D:
D02000
First response storage word
C:
D00000
+0:
000C hex
Command data bytes: 0004 hex (4 bytes decimal)
+1:
000A hex
Response data bytes: 0004 hex (4 bytes decimal)
+2:
0005 hex
Send destination network address: 05 hex; Serial port number: 0 hex (not used)
+3:
0200 hex
Send destination node address: 02 hex (set the unit number for Host Link + 1); Send
destination unit address: 00 hex
+4:
0000 hex
Response required; Communications port number: 0; Resends: 0 hex
+5:
0000 hex
Response monitoring time: 2 s
Operand
Offset
Value
Meaning
D:
D02000
+0:
0402 hex
Change operating mode (stop operation) (FINS command code: 0402 hex)
+1:
FFFF hex
FINS end code: FFFF hex (normal end)
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...