154
Setup Area Allocations
Section 5-2
5-2-2
Setup Area Allocations
m = 100
×
unit number
Port Settings
The setting for the port settings determines if the default settings or user set-
tings will be used for port 1 and port 2. Be sure to use the same settings as
the RS-232C port on the host computer connected via the Host Link System.
If the default port settings are specified, then the settings of bits 00 to 04 and
the baud rate in D32001 will be ignored.
The default settings used are as follows: Baud rate: 9,600 bps, start bits:
1 bit, data length: 7 bits, parity: even, and stop bits: 2 bits.
DM Area
Bit
Setting contents
Boards
(CS Series only)
Units
(CS/CJ Series)
Port 1
Port 2
Port 1
Port 2
D32000
D32010
m
m + 10
15
Port settings
0: Defaults, 1: User settings
12 to 14
Reserved
08 to 11
Serial communications mode
6: Protocol macro
05 to 07
Reserved
04
Start bits
0: 1 bit; 1: 1 bit
(1 start bit is always used regardless of this setting)
03
Data length
0: 7 bits; 1: 8 bits
02
Stop bits
0: 2 bits; 1: 1 bit
01
Parity
0: Yes; 1: No
00
Parity
0: Even; 1: Odd
D32001
D32011
m + 1
m + 11
00 to 03
Baud rate (Unit: bps)
0: Default (9,600)
3: 1,200
4: 2,400
5: 4,800
6: 9,600
7: 19,200
8: 38,400
(The following setting can be selected even if protocol macro is set
as the serial communications mode: Unit Ver. 1.2 or later only)
9: 57,600
D32007
D32017
m + 7
m + 17
08 to 15
Serial Gateway response timeout monitoring time (Unit Ver. 1.2 or
later only)
0 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
Unit: 100 ms
00 to 07
Serial Gateway send start timeout monitoring time (Unit Ver. 1.2 or
later only)
0 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
Unit: 100 ms
D32008
D32018
m + 8
m + 18
15
Transmission method
0: Half-duplex; 1: Full-duplex
00 to 14
Reserved
03
Clearing/holding the contents of the reception buffer in full-duplex
mode (Unit Ver. 1.2 or later only)
0: Clear; 1: Hold
02
Link word specification data exchange timing (Unit Ver. 1.2 or later
only)
0: On-request I/O refreshing
1: Continuos I/O refreshing
00 to 01
Reserved
D32009
D32019
m + 9
m + 19
00 to 15
Maximum number of bytes in send/receive data:
00C8 to 03E8 Hex
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...