3
Installa
tion
3-4
■
AC IN and ground terminals
3.2 AC power connector wiring
■
Requirements
Prepare the following to wire power connectors.
Connector (provided)
Connection lever (provided)
or flat-blade screwdriver.
Wire
■
Wiring methods
Strip the wire sheath to expose 8 to 9 mm of bare lead.
Use either of the methods shown below to insert the wire core into the opening in the power connector, and then ensure
that the wire does not come out.
Strip 8 to 9 mm of sheath.
8 – 9 mm
Connection lever
If using connection lever provided.
If using flat-blade screwdriver.
The wire can be inserted while using
the flat-blade screwdriver to press
down the spring from the opening on
the top of the connector.
CAUTION
As a rule, only connect a single wire to each wire opening.