82
Connecting to the RS-232C Port at the Host
Section 4-1
S
Settings at the host
The setting methods for each unit are as follows.
S
Connecting to a C-series C200HS, C200HX/HG/HE(-ZE), CPM1, CQM1,
SRM1
[PC system setting area settings]
Write the “PC system setting area” (data memory) settings directly from a pe-
ripheral tool (e.g. SYSMAC support software) in accordance with the host
model and port.
Host Model
Word #
Writing Value
Setting
RS-232C port of C200HS,
C200HX/HG/HE(-ZE), CQM1, SRM1
DM6645
Port A of C200HX/HG/HE(-ZE)
(*1)
DM6555
4000
Use NT link
Port B of C200HX/HG/HE(-ZE)
(*1)
DM6550
4000
(1:1)
CPM1
DM6650
*1 RS-232C port of the communication board
For details on operations relating to the “PC system setting area”, refer to the
manual for the PC which is used.
[Setting the DIP switches on the front of a C200HX/HG/HE(-ZE)]
When using a C200HX/HG/HE(-ZE) or CQM1, the DIP switches on the front
panel must be set as shown below in order to make the settings in the “PC
system setting area” (data memory) effective.
C200HX/HG/HE-(Z)E
CQM1
RS-232C port communication condition setting
Set DIP SW5 to “OFF” to make the settings
made in PC system setting effective.
OFF
ON
1
2
3
4
5
6
1
2
3
4
5
6
ON
OFF
ON
ON
[Setting the switches on a CPM1 RS-232C adapter]
CPM1-
CIF01
Set the mode setting switch to “NT” (lower position).
Содержание NT31 Series
Страница 1: ...Cat No V043 E1 2 Programmable Terminal NT31 31C OPERATION MANUAL...
Страница 2: ...iii NT31 31C Programmable Terminal Operation Manual Produced March 1999...
Страница 41: ...30 Before Operating Section 1 5...
Страница 75: ...64 Using a Memory Unit NT31 NT31C without V1 Section 3 6...
Страница 160: ...149...
Страница 174: ...163...
Страница 193: ...182...
Страница 211: ...200...
Страница 235: ...224 c Return to the screen on which screens are specified...
Страница 262: ...251...
Страница 284: ...273 The printer type control protocol and printing method are set with the memory switches of the NT31 NT31C...
Страница 347: ...336 Screen number 5 is set for touch switch 1 To next screen When touch switch 1 is pressed Screen number 5...
Страница 360: ...349 It is not possible to control a gloval window by touch switch operation...
Страница 375: ...364 For details on the method of display depending on the General settings refer to Common Attributes page 358...
Страница 391: ...380 1 The 100 value 0 value and 100 value must comply with the following relationship 100 value 0 value 100 value...
Страница 468: ...457 254 255 0 2 7 1 4 5 3 3 0 0 0 5 9 8 0 3...
Страница 476: ...465 Special Functions Section 7 16...
Страница 495: ...484 OFF...
Страница 610: ...599 Commands Responses Section 9 3...
Страница 630: ...619 Examples of Actual Applications of Memory Link Section 10 2...