![Omron NT31 Series Скачать руководство пользователя страница 543](http://html1.mh-extra.com/html/omron/nt31-series/nt31-series_operation-manuals_744552543.webp)
532
Input of Numeric Values and Character Strings
Section 8-7
Inputting Numeric Values Using a Thumbwheel Type Input Field
The following describes the procedure for inputting a numeric value into a thumb-
wheel type input field.
Increase by “1” when key is touched
1 2 3 4
– – – –
+ + + +
+
Decrease by “1” when key is touched
–
[Setting]
When creating a screen using the Support Tool, register the following element for
the screen.
- Numeral setting input field (thumbwheel type)
Reference: Since a thumbwheel type numeral setting field itself has a touch switch for input-
ting a numeric value, it is not necessary to register other elements for inputting a
numeric value.
[Operation]
(1) Display a screen which has a thumbwheel type numeral setting field.
(2) Change the numeric value using the increment/decrement (+,
−
) keys pro-
vided at the top and bottom of each digit position of the thumbwheel type nu-
meral setting field.
For the procedure for changing a numeric value, refer to “Using a thumbwheel
type input field” (page 533).
Reference
- In a thumbwheel type numeral setting field, a numeric value is confirmed imme-
diately after it is changed and written to a numeral setting field. At the same
time, the occurrence of a change in the contents of the numeral setting memory
table is notified to the host.
- When a thumbwheel type numeral setting field is displayed, the numeric value
which has been stored in the numeral memory table prior to the input is dis-
played.
- Even if more than one thumbwheel type numeral setting field exists on a screen,
specification of an objective input field is not necessary since input is performed
by using the thumbwheel switch in the required input field.
- If the “upper/lower (max./min.) limit check” function is set for the numeral setting
input field, the function checks if the input numeric value falls within the specified
range when the input is confirmed. If the numeric value is outside the specified
range, the buzzer sounds three times, the input numeric value is canceled, and
the screen returns to the display before starting the input. In this case, neither
writing to a numeral memory table nor notification to the host is executed.
Содержание NT31 Series
Страница 1: ...Cat No V043 E1 2 Programmable Terminal NT31 31C OPERATION MANUAL...
Страница 2: ...iii NT31 31C Programmable Terminal Operation Manual Produced March 1999...
Страница 41: ...30 Before Operating Section 1 5...
Страница 75: ...64 Using a Memory Unit NT31 NT31C without V1 Section 3 6...
Страница 160: ...149...
Страница 174: ...163...
Страница 193: ...182...
Страница 211: ...200...
Страница 235: ...224 c Return to the screen on which screens are specified...
Страница 262: ...251...
Страница 284: ...273 The printer type control protocol and printing method are set with the memory switches of the NT31 NT31C...
Страница 347: ...336 Screen number 5 is set for touch switch 1 To next screen When touch switch 1 is pressed Screen number 5...
Страница 360: ...349 It is not possible to control a gloval window by touch switch operation...
Страница 375: ...364 For details on the method of display depending on the General settings refer to Common Attributes page 358...
Страница 391: ...380 1 The 100 value 0 value and 100 value must comply with the following relationship 100 value 0 value 100 value...
Страница 468: ...457 254 255 0 2 7 1 4 5 3 3 0 0 0 5 9 8 0 3...
Страница 476: ...465 Special Functions Section 7 16...
Страница 495: ...484 OFF...
Страница 610: ...599 Commands Responses Section 9 3...
Страница 630: ...619 Examples of Actual Applications of Memory Link Section 10 2...