626
Responding to Displayed Error Messages
Section 11-2
11-2-2
Errors Occurring during Operation and Their Remedies
The table below shows the errors that can occur during operation of the
NT31/NT31C and their remedies.
Message
Cause
Remedy
[Address Setting Error]
Addressing Error exists in the
Screen.
Correct address setting by the
Support Tool.
The host side allocated words
and bits set with the Support Tool
are incorrect.
Set correct words and bits after checking the area
used at the host side by referring to APPENDIX L
“PC Memory Map” (page 684), and the manual for
the PC being used.
[Memory Table No. Error]
Memory table No. is out of limit.
Correct the table No. by the
Support Tool.
The memory table number set
with the Support Tool is outside
the range for the number of
memory tables set in the system
memory.
Either increase the number of memory tables in
the “System” settings under “PT Configuration” at
the Support Tool, or set the memory table number
again within the established range.
[Programming Console Error]
Setting of Programming Console
Function is inadequate.
Confirm the PC model and
The communication settings are
incorrect.
Set the communication method/communication
port as follows when using the programming
console function.
- With C series PLC : NT Link : 1 : 1
- With CS1 series PLC : NT Link : 1 : N
comm. protocol.
The PC used does not support
the programming console
function.
Not all PCs support the programming console
function. Check the model of the PC you are
using. (6-12 “Programming Console Function”,
page 242)
[Programming Consol Error]
PROGRAMMING CONSOLE
function does not RUN.
The connecting cable is
defective.
Check the cable connection and perform a
conductivity test. If there is a fault, replace the
cable.
function does not RUN.
It can be caused by:
S
faulty connecting cable.
S
Malfunction due to external noise
Carry out grounding work in accordance with the
conditions by referring to 3-1-4 “Grounding”, page
40.
S
Protocol mismatch between
the PT and PC.
Set the PC to NT LINK 1:1.
A programming console is
connected.
It is not possible to use a programming console
and the programming console function at the
same time. Disconnect the programming console.
The communication conditions at
the PC have been changed in
accordance with the
NT31/NT31C programming
console function.
Set the communication conditions at the PC to
match the conditions set in the System Menu.
Содержание NT31 Series
Страница 1: ...Cat No V043 E1 2 Programmable Terminal NT31 31C OPERATION MANUAL...
Страница 2: ...iii NT31 31C Programmable Terminal Operation Manual Produced March 1999...
Страница 41: ...30 Before Operating Section 1 5...
Страница 75: ...64 Using a Memory Unit NT31 NT31C without V1 Section 3 6...
Страница 160: ...149...
Страница 174: ...163...
Страница 193: ...182...
Страница 211: ...200...
Страница 235: ...224 c Return to the screen on which screens are specified...
Страница 262: ...251...
Страница 284: ...273 The printer type control protocol and printing method are set with the memory switches of the NT31 NT31C...
Страница 347: ...336 Screen number 5 is set for touch switch 1 To next screen When touch switch 1 is pressed Screen number 5...
Страница 360: ...349 It is not possible to control a gloval window by touch switch operation...
Страница 375: ...364 For details on the method of display depending on the General settings refer to Common Attributes page 358...
Страница 391: ...380 1 The 100 value 0 value and 100 value must comply with the following relationship 100 value 0 value 100 value...
Страница 468: ...457 254 255 0 2 7 1 4 5 3 3 0 0 0 5 9 8 0 3...
Страница 476: ...465 Special Functions Section 7 16...
Страница 495: ...484 OFF...
Страница 610: ...599 Commands Responses Section 9 3...
Страница 630: ...619 Examples of Actual Applications of Memory Link Section 10 2...