D.3 UL Standards
The UL/cUL mark applies to products in the United States and Canada indicates that UL has performed product testing
and evaluation and determined that their stringent standards for product safety have been met. For a product to receive UL
certification, all components inside that product must also receive UL certification.
UL
C
R
US
LISTED
Figure D.7 UL/cUL Mark
u
UL Standards Compliance
This drive is tested in accordance with UL standard UL508C, E131457 and complies with UL requirements. The following
conditions must be met to maintain compliance when using this drive in combination with other equipment:
n
Installation Area
Do not install the drive to an area greater than pollution severity 2 (UL standard).
n
Main Circuit Terminal Wiring
OYMC recommends using UL-listed copper wires (rated at 75 °C) and closed-loop connectors or CSA-certified ring
connectors sized for the selected wire gauge to maintain proper clearances when wiring the drive. Use the correct crimp
tool to install connectors per manufacturer recommendation.
Table D.5
lists a suitable closed-loop connector manufactured
by JST Corporation.
Table D.5 Closed-Loop Crimp Terminal Size (JIS C 2805) (same for 200 V and 400 V)
Wire Gauge
mm
2
(AWG)
Terminal
Screws
Crimp Terminal
Model Numbers
Tightening Torque
N m (lb to in.)
0.75 (18)
M3.5
R1.25-3.5
0.8 to 1.0 (7.1 to 8.9)
M4
R1.25-4
1.2 to 1.5 (10.6 to 13.3)
1.25 (16)
M3.5
R1.25-3.5
0.8 to 1.0 (7.1 to 8.9)
M4
R1.25-4
1.2 to 1.5 (10.6 to 13.3)
2 (14)
M3.5
R2-3.5
0.8 to 1.0 (7.1 to 8.9)
M4
R2-4
1.2 to 1.5 (10.6 to 13.3)
3.5/5.5 (12/10)
M4
R5.5-4
1.2 to 1.5 (10.6 to 13.3)
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
Table D.6 Recommended Input Fuse Selection
Drive Model
JZA
Class T Fuses
Class L Fuses
Model
Fuse Ampere Rating
Model
Fuse Ampere Rating
200 V Class Single-Phase Drives
B0P1
A6T15
15
CR6L-20/UL
20
B0P2
A6T20
20
CR6L-30/UL
30
B0P4
A6T20
20
CR6L-50/UL
50
B0P7
A6T40
40
CR6L-75/UL
75
B1P5
A6T40
40
CR6L-100/UL
100
200 V Class Three-Phase Drives
20P1
A6T10
10
CR6L-20/UL
20
20P2
A6T10
10
CR6L-20/UL
20
20P4
A6T15
15
CR6L-20/UL
20
20P7
A6T20
20
CR6L-30/UL
30
21P5
A6T25
25
CR6L-50/UL
50
22P2
A6T30
30
CR6L-50/UL
50
24P0
A6T40
40
CR6L-75/UL
75
400 V Class Three-Phase Drives
40P2
A6T10
10
CR6L-20/UL
20
40P4
A6T10
10
CR6L-20/UL
20
40P7
A6T20
20
CR6L-50/UL
50
41P5
A6T25
25
CR6L-50/UL
50
42P2
A6T25
25
CR6L-50/UL
50
43P0
A6T25
25
CR6L-50/UL
50
D.3 UL Standards
218
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...