Overload Tolerance
Overload Characteristics
Cooling Ability
100
150
110
100120 167 200
55
50
0
Rated Speed=100% Speed
60 sec.
Continuous
A
D
B
(60 Hz)
Speed (%)
Torque (%)
Motor is designed to effectively cool
itself even at low speeds (as lower as 6
Hz).
Continuous operation with 100%
load from 6 Hz to 50/60 Hz.
n
L1-02: Motor Overload Protection Time
Sets the time it takes the drive to detect motor overheat due to overload. This setting rarely requires adjustment, but should
correlate with the motor overload tolerance protection time for performing a hot start.
No.
Name
Setting Range
Default
L1-02
Motor Overload Protection Time
0.1 to 5.0 min
1.0 min
• Defaulted to operate with an allowance of 150% overload operation for one minute.
•
Figure 5.34
shows an example of the electrothermal protection operation time using a general-purpose motor operating
at 60 Hz with L1-02 set to one minute.
Operation time (minutes)
Cold start
Hot start
Motor current (%)
E2-01 = 100% m o t o r c u r r e n t
10
7
3
1
0.4
0.1
0
100
150
200
Figure 5.34 Motor Protection Operation Time
n
L1-13: Continuous Overload Detection Selection
Determines whether or not to hold the current value of the electrothermal motor protection (L1-01) when the power supply
is interrupted.
No.
Name
Setting Range
Default
L1-13
Continuous Electronic Thermal Overload Protection Selection
0 or 1
1
Setting 0: Disabled
Setting 1: Enabled
u
L2: Momentary Power Loss Ride-Thru
n
L2-01: Momentary Power Loss Operation Selection
When a momentary power loss occurs the drive can be set to automatically return to the operation it was performing when
the power went out based on certain conditions.
No.
Name
Setting Range
Default
L2-01
Momentary Power Loss Operation Selection
0 to 2
0
Setting 0: Disabled (default)
If power is not restored within 15 ms, a Uv1 fault will result and the drive will stop the motor.
5.7 L: Protection Functions
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
103
5
Parameter Details
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...