A.6 Drive Derating Data
The drive can be operated at above rated temperature, altitude and default carrier frequency by derating the drive capacity.
u
Temperature Derating
As the ambient temperature for the drive is increased above the drive specification the drive should be derated. Additionally
parameter L8-35 Installation Method Selection on page
168
should be set according to enclosure type and mounting method
as illustrated in
Figure A.1
on page
168
.
n
Output Current Derating Due to Ambient Temperature
If the ambient temperature is above the drive specification or if drives are side-by-side mounted in a cabinet, the parameters
L8-12 and L8-35 must be set according to the installation conditions. The output current is derated as shown in
Figure
A.1
.
No.
Name
Description
Range
Def.
L8-12
Ambient
Temperature Setting
Adjust the drive overload (oL2) protection level when the drive is installed
in an environment that exceeds its ambient temperature rating.
-10 to 50
30 °C
L8-35
Installation Method
Selection
0: IP20/Open-Chassis Drive
1: Side-by-Side Mounting
2: NEMA Type 1 Drive
3: Finless Drive or External Heatsink Installation
0 to 3
0
40
50
0
30
o
35
50%
70%
80%
85%
100%
o
o
o
Drive
Rating
Ambient tem
p C
Parameter L8-12
Parameter L8-35 = 0 (IP20/Open-Chassis Drive)
Parameter L8-35 = 2
(NEMA Type 1 Drive)
Parameter L8-35 = 1
(Side-by-side Mounting)
Parameter L8-35 = 3
(Finless Drive or External
Heatsink Installation)
Figure A.1 Ambient Temperature and Installation Method Derating
A.6 Drive Derating Data
168
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...