D.2 European Standards
Figure D.1 CE Mark
The CE mark indicates compliance with European safety and environmental regulations and is required for engaging in
business and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics
manufacturers and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
•
EMC Guidelines:
2004/108/EC
•
Low Voltage Directive:
2006/95/EC
u
CE Low Voltage Directive Compliance
This drive has been tested according to IEC61800-5-1:2007, and it fully complies with the Low Voltage Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other
devices:
n
Area of Use
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC664.
n
Installing Fuses on the Input Side
Always install input fuses. Select fuses according to
Table D.1
.
Table D.1 Recommended Input Fuse Selection
Drive Model
JZA
Class T Fuses
Model
Fuse Ampere Rating
200 V Class Single-Phase Drives
B0P1
A6T15
15
B0P2
A6T20
20
B0P4
A6T20
20
B0P7
A6T40
40
B1P5
A6T40
40
200 V Class Three-Phase Drives
20P1
A6T10
10
20P2
A6T10
10
20P4
A6T15
15
20P7
A6T20
20
21P5
A6T25
25
22P2
A6T30
30
24P0
A6T40
40
400 V Class Three-Phase Drives
40P2
A6T10
10
40P4
A6T10
10
40P7
A6T20
20
41P5
A6T25
25
42P2
A6T25
25
43P0
A6T25
25
44P0
A6T30
30
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your dealer for instructions.
u
EMC Guidelines Compliance
This drive is tested according to IEC61800-3:2004 and it complies with the EMC guidelines.
D.2 European Standards
212
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...