5.9 o: Operator Related Settings
These parameters concern the various functions and features of the digital operator.
u
o1: Display Settings and Selections
These parameters determine how data is shown on the operator display.
n
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter will be displayed upon power up. Defaulted to show the frequency reference when the
drive is first turned on.
No.
Name
Setting Range
Default
o1-02
User Monitor Selection after Power Up
1 to 4
1
Setting 1: Frequency Reference (U1-01)
Setting 2: Forward/Reverse
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
n
o1-03: Digital Operator Display Selection
Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
• U1-01: frequency reference
• U1-02: output frequency
• d1-01 to d1-08: frequency references
No.
Name
Setting Range
Default
o1-03
Digital Operator Display Selection
0 to 1
0
Setting 0: Hz
The frequency reference and monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: %
The frequency reference and monitors are displayed as a percentage with a resolution of 0.01%. 100% is equal to the
maximum output frequency.
u
o2: Operator Key Selections
These parameters determine the functions assigned to the operator keys.
n
o2-02: STOP Key Function Selection
Selects if the STOP key on the digital operator can be used to stop the operation when the drive is controlled from a remote
source (i.e., not from digital operator).
No.
Name
Setting Range
Default
o2-02
STOP Key Function Selection
0 or 1
1
Setting 0: Disabled
The STOP key has no function when the drive is controlled by a source other than the digital operator. The drive can only
be stopped from the Run command source that has been selected.
Setting 1: Enabled
The STOP key can be used to terminate the operation, even if the Run command source is not assigned to the digital
operator. If operation has been interrupted by pressing the STOP key, the Run command must be cycled to restart the drive.
n
o2-04: Drive Model Selection
Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is important for optimal
performance and proper protection for the drive hardware. This parameter is configured at the factory and does not normally
require adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage.
5.9 o: Operator Related Settings
112
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...