Output
frequency
2 Hz
Frequency
Detection 2
ON
OFF
2 Hz
L4-01
L4-01
Figure 5.24 Frequency Detection 2 Time Chart
Refer to L4-01: Speed Agreement Detection Level on page 106
for details on setting the detection width.
Setting 6: Drive Ready
Output closes whenever the drive is ready to operate the motor.
Status
Description
Open
During power up, initialization, fault or in Programming Mode (while b1-08 = 0 or 2).
Closed
Drive is ready for operation.
Refer to b1-08: Run Command Selection while in Programming Mode on page 75
for details on the setting of b1-08.
Setting 7: DC Bus Undervoltage
Output closes whenever the DC bus voltage or control circuit power supply drops below the trip level. The undervoltage
trip level depends on the setting of parameter E1-01. Refer to E1-01 for details. A fault in the DC bus charge circuit will
also cause the DC Bus Undervoltage output to close.
Status
Description
Open
DC bus voltage is above the undervoltage level.
Closed
DC bus voltage has fallen below the undervoltage level.
Setting 8: During Baseblock (N.O.)
Output closes to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors are not
switched and no voltage will be output.
Status
Description
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Settings B and 17: Torque Detection (N.O./N.C.)
These digital output functions can be used to signal an overtorque situation to an external device.
Set up the torque detection and select the output function from the table below.
Refer to L6: Torque Detection on page
108
for details.
Setting
Status
Description
B
Closed
Torque Detection (N.O.):
Output current/torque exceeds the torque value set in parameter L6-02 for longer than the time specified in
parameter L6-03.
17
Open
Torque Detection (N.C.):
Output current/torque exceeds the torque value set in parameter L6-02 for longer than the time specified in
parameter L6-03.
Setting E: Fault
The Fault configured digital output will close whenever the drive experiences a fault (this excludes faults CPF00 and
CPF01).
Setting F: Not Used
Use this setting when the terminal is not used or when using the terminal as a throughput.
When set to “F”, the output is not set by any drive function but it can be switched by a PLC via MEMOBUS/Modbus
communications interface (through mode).
Setting 10: Minor Fault
Output closes when a minor fault condition is present.
5.6 H: Terminal Functions
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
97
5
Parameter Details
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...