n
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to analog input A1 and also to the reference
value from potentiometer option (AI-V3/J).
No.
Name
Setting Range
Default
H3-13
Analog Input Filter Time Constant
0.00 to 2.00 s
0.03 s
An analog input filter can be used to prevent erratic drive control when a “noisy” analog reference is used. The drive
operation becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog
signals.
u
H4: Multi-Function Analog Output Terminal AM
These parameters assign a function to analog output terminal AM for monitoring a specific aspect of drive performance.
n
H4-01: Multi-Function Analog Terminal AM Monitor Selection
Sets the desired drive monitor parameter U
-
to output as an analog value via terminal AM.
Refer to U:
Monitors on page 181
for a list of all monitors. The “Analog Output Level” columns indicates if a monitor can be applied
for analog output.
Example: Enter “103” for U1-03.
No.
Name
Setting Range
Default
H4-01
Multi-Function Analog Terminal AM Monitor Selection
000 to 999
102
A setting of 031 or 000 applies no drive monitor to the analog output. With this setting the terminal AM output level can
be set by a PLC via a MEMOBUS/Modbus communications interface (through mode).
n
H4-02/H4-03: Multi-Function Analog Output Terminal AM Gain/Bias
Parameter H4-02 sets the output voltage that is equal to 100% of the monitor value. Parameter H4-03 sets the output voltage
equal to 0% of the monitor value.
Both values are set as a percentage of 10 V. The minimum output voltage for terminal AM is 0 V, the maximum is 10
Vdc.
Figure 5.32
illustrates the function of the gain and bias settings.
No.
Name
Setting Range
Default
H4-02
Multi-Function Analog Output Terminal AM Gain
-999.9 to 999.9%
100.0%
H4-03
Multi-Function Analog Output Terminal AM Bias
-999.9 to 999.9%
0.0%
0 V
3 V
10 V
Bias 30%
Gain 100%
Bias 0%
Gain 100%
100%
Monitor value
0%
Gain 50%
Bias 0%
Terminal AM
output
voltage
0 V
5 V
10 V
Gain 150%
Bias 0%
Gain 100%
Bias 0%
100%
Monitor value
0%
Terminal AM
output
voltage
Figure 5.32 Analog Output Gain/Bias Setting
When viewing the settings for H4-02, terminal AM will output a voltage that is equal to 100% of the monitor value
(considering the present setting). When viewing the settings for H4-03, terminal AM will output a voltage that is equal to
0% of the monitor value.
u
H5: MEMOBUS/Modbus Serial Communication
Through the drives optional RS-422/485 interface, serial communication can be performed with programmable logic
controllers (PLCs) or similar devices using the MEMOBUS/Modbus protocol.
The H5-
parameters are used to set up the drive for MEMOBUS/Modbus Communications.
Refer to MEMOBUS/
Modbus Serial Communication on page 191
for detailed descriptions of the H5-
parameters.
5.6 H: Terminal Functions
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
101
5
Parameter Details
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...