4.5 Powering Up the Drive
u
Powering Up the Drive and Operation Status Display
n
Powering Up the Drive
Review the following checklist before turning the power on.
Item to Check
Description
Power supply voltage
Ensure the power supply voltage is correct:
200 V class: single-phase 200 to 240 Vac 50/60 Hz
200 V class: 3-phase 200 to 240 Vac 50/60 Hz
400 V class: 3-phase 380 to 480 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).
(for single-phase 200 V class models, wire only R/L1 and S/L2)
Check for proper grounding of drive and motor.
Drive output terminals
and motor terminals
Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.
Control circuit terminals
Check control circuit terminal connections.
Drive control terminal status
Open all control circuit terminals (off).
Status of the load
and connected machinery
Uncouple the motor from the load.
n
Status Display
When the power supply to the drive is turned on, the LED operator lights will appear as follows:
No.
Name
Description
Normal
Operation
STOP
The data display area displays the frequency reference.
is lit.
Fault
STOP
Main circuit low voltage (ex)
Data displayed varies by the type of fault.
Refer to Fault Displays, Causes and Possible
Solutions on page 123
for more information and possible solution.
and
are lit.
u
V/f Pattern Setting
Setting the V/f pattern according to the application.
Refer to E: Motor Parameters on page 86
for details on setting the
V/f pattern.
n
Notes when Setting the V/f Pattern
Set the maximum output frequency to match the motor characteristics.
If the V/f pattern voltage is increased motor torque may also increase. However, if the V/f voltage is set too high these
problems may occur:
• Excessive motor current.
• Motor overheat or vibration.
4.5 Powering Up the Drive
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
63
4
Start-Up Programming & Operation
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...