Cause
Possible Solutions
Minor Fault
Output
(H2-01 = 10)
MEMOBUS/Modbus test has finished
normally.
This verifies that the test was successful.
No output
LED Operator Display
Minor Fault Name
SE
MEMOBUS/Modbus Communication Test Mode Error
Cause
Possible Solutions
Minor Fault
Output
(H2-01 = 10)
A digital input programmed to 67H
(MEMOBUS/Modbus test) was closed
while the drive was running.
Stop the drive and run the test again.
No output
LED Operator Display
Minor Fault Name
Uv
Undervoltage
One of the following conditions was true when the drive was stopped and a run command was entered:
• DC bus voltage dropped below the under voltage detection level.
• Contactor to suppress inrush current in the drive was open.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus
voltage is below the detection level.
Cause
Possible Solutions
Minor Fault
Output
(H2-01 = 10)
Phase loss in the drive input power.
Check for wiring errors in the main circuit drive input power. Correct the wiring.
YES
Loose wiring in the drive input power
terminals.
• Ensure the terminals have been properly tightened.
• Apply the tightening torque specified in this manual to fasten the terminals.
Refer to
Wire Gauges and Tightening Torque on page 37
YES
There is a problem with the drive input
power voltage.
• Check the voltage.
• Lower the voltage of the drive input power so that it is within the limits listed in the
specifications.
YES
Drive internal circuitry is worn.
• Check the maintenance time for the capacitors (U4-05).
• Replace the drive if U4-05 exceeds 90%.
YES
The drive input power transformer is not
large enough and voltage drops when the
power is switched on.
• Check for a tripped alarm when the magnetic contactor, line breaker and leakage
breaker are turned on.
• Check the capacity of the drive input power transformer.
YES
Air inside the drive is too hot.
• Check the temperature inside the drive.
YES
The CHARGE indicator light is broken or
disconnected.
• Replace the drive.
YES
6.5 Alarm Detection
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
131
6
Troubleshooting
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...