3.10 Braking Resistor
Dynamic braking (DB) helps bring the motor to a smooth and rapid stop when working with high inertia loads. As the
drive lowers the frequency of a motor with high inertia connected, regeneration occurs. This can cause an overvoltage
situation when the regenerative energy flows back into the DC bus capacitors. A braking resistor prevents these overvoltage
faults.
NOTICE: Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit.
Carefully review the braking resistor instruction manual when connecting a braking option to the drive.
Note:
The braking circuit must be sized properly in order to dissipate the power required to decelerate the load in the desired time. Ensure that
the braking circuit can dissipate the energy for the set deceleration time prior to running the drive.
NOTICE: Use a thermal overload relay or an over-temperature contact to interrupt input power to the drive in the event the braking
resistor overheats. In the event of a possible thermal overload, the relay will trigger the input contactor and prevent the braking resistor
from burning up.
u
Installation
WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect a braking resistor directly to any
other terminals. Improper wiring connections could result in death or serious injury by fire. Failure to comply may result in damage to
the braking circuit or drive.
NOTICE: Connect braking resistors to the drive as shown in the I/O wiring examples. Improperly wiring braking circuits could result in
damage to the drive or equipment.
n
Installation Procedure
1.
Disconnect all electrical power to the drive and wait at least one minute before servicing the drive and any
connected components.
2.
Remove drive front cover.
3.
Use a voltmeter to verify that voltage is disconnected from incoming power terminals and that the DC bus no
longer holds a charge.
Power
supply
Thermal
relay
Motor
Drive
Braking resistor
Thermal relay switch for
external braking resistor
Fault contact
MC
SA
SA
SA
MC
ON
MC
OFF
THRX
THRX
TRX
MC
TRX
MA MC
R/L1 B1
B2
S/L2
T/L3
U/T1
V/T2
W/T3
MCCB
Figure 3.20 Connecting a Braking Resistor
4.
Follow manufacturer instructions to connect the resistor unit to the drive using proper wire gauge according to
local electrical codes.
Power leads for the remote mount resistors generate high levels of electrical noise; group these signal leads
separately.
5.
Mount the resistor unit on a noncombustible surface. Maintain minimum side and top clearances according to
resistor manufacturer instructions.
WARNING! Fire Hazard. Do not use improper combustible materials. Failure to comply could result in death or serious injury
by fire. Attach the drive or braking resistors to metal or other noncombustible material.
6.
Reinstall drive covers and resistor covers, if provided.
7.
Set parameter L3-04 = “0” to disable stall prevention during deceleration.
Set parameter L8-01 to “1” to enable overheat protection when using a heatsink-mounted braking resistor option.
Set L8-01 = “0” for other braking resistor types.
Table 3.14 Braking Resistor Settings
Parameter
Settings
L8-01: Internal Dynamic Braking Resistor Protection Selection
0: Disabled. The drive will not provide overheat protection.
Supply separate means of overheat protection.
1: Enabled. Braking Resistor is protected from overheat.
L3-04: Stall Prevention During Deceleration
0: Stall prevention disabled.
8.
Operate the system and verify the required deceleration rate is obtained during dynamic braking or stopping.
3.10 Braking Resistor
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
47
3
Electrical Installation
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...