C.12 Communication Errors
u
MEMOBUS/Modbus Error Codes
A list of MEMOBUS/Modbus errors appears below.
When an error occurs, remove whatever caused the error and restart communications.
Error Code
Error Name
Cause
01H
Function Code Error
• Attempted to set a function code from a PLC other than 03H, 08H, and 10H.
02H
Register Number Error
• A register number specified in the command message does not exist.
• Attempted to send a broadcast message using other register numbers than 0001H or 0002H.
03H
Bit Count Error
• Read data or write data is greater than 16 bits. Invalid command message quantity.
• In a write message, the “Number of Data Items” contained within the message does not equal twice the amount of data
words (i.e., the total of Data 1+ Data 2, etc.).
21H
Data Setting Error
• Control data or parameter write data is outside the allowable setting range.
• Attempted to write a contradictory parameter setting.
22H
Write Mode Error
• Attempted to write while the drive was operating to a parameter that cannot be written to during run.
• During an EEPROM data error (CPF06), the master attempted to write to a parameter other than A1-00 to -05, E1-03, or
o2-04.
• Attempted to write to read-only data.
23H
DC Bus Undervoltage Write Error
• Attempted to write from the master during an undervoltage fault (Uv1).
• Attempted to execute and Enter command during Uv1.
24H
Write Error During Parameter Process
• Master attempted writing to the drive while the drive was processing parameter data.
u
Slave Not Responding
In the following situations, the slave drive will ignore the command message sent from the master, and not send a response
message:
• When a communications error (overrun, framing, parity or CRC-16) is detected in the command message.
• When the slave address in the command message and the slave address in the drive do not match (remember to set the
slave address for the drive using H5-01).
• When the gap between two blocks (8 bit) of a message exceeds 24 bits.
• When the command message data length is invalid.
Note:
If the slave address specified in the command message is 00H, all slaves execute the write function, but do not return response messages
to the master.
C.12 Communication Errors
206
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...