u
Monitor Data
Monitor data can be read only.
Register No.
Contents
0020H
Drive Status 1
bit 0
During Run
bit 1
During Reverse
bit 2
Drive Ready
bit 3
Fault
bit 4
Data Setting Error
bit 5
Multi-Function Contact Output (terminal MA/MB-MC)
bit 6 to bit D
Reserved
bit E
ComRef status
bit F
ComCtrl status
0021H
Fault Contents 1
bit 0
Overcurrent (oC)
bit 1
Overvoltage (ov)
bit 2
Drive Overload (oL2)
bit 3
Overheat 1 (oH1)
bit 4
Braking Resistor Overheat (rH)
bit 5, 6
Reserved
bit 7
EF0 to 5: External Fault
bit 8
CPF
: Hardware Fault (includes oFx)
bit 9
Motor Overload (oL1), Overtorque Detection 1 (oL3)
bit A
Reserved
bit B
Main Circuit Undervoltage (Uv)
bit C
Undervoltage (Uv1), Soft Charge Circuit Fault (Uv3)
bit D
Output Phase Loss (LF), Input Phase Loss (PF)
bit E
MEMOBUS/Modbus Communication Error (CE)
bit F
Operator Connection Fault (oPr)
0022H
Data Link Status
bit 0
Writing data or switching motors
bit 1
Reserved
bit 2
bit 3
Upper or lower limit error
bit 4
Data conformity error
bit 5
Writing to EEPROM
bit 6 to bit F
Reserved
0023H
Frequency Reference,
<1>
0024H
Output Frequency,
<1>
0025H
Output Voltage Reference, 0.1 V units
0026H
Output Current
0027H
Reserved
0028H
Reserved
0029H
Fault Contents 2
bit 0, 1
Reserved
bit 2
Input Phase Loss (PF)
bit 3
Output Phase Loss (LF)
bit 4
Braking Resistor Overheat (rH)
bit 5 to bit F
Reserved
002AH
Alarm Contents1
bit 0 to bit 1
Reserved
bit 2
Run Command Input Error (EF)
bit 3
Drive Baseblock (bb)
bit 4
Overtorque Detection 1 (oL3)
bit 5
Heatsink Overheat (oH)
bit 6
Overvoltage (ov)
bit 7
Undervoltage (Uv)
bit 8
Reserved
bit 9
MEMOBUS/Modbus Communication Error (CE)
bit A to F
Reserved
C.10 MEMOBUS/Modbus Data Table
200
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Содержание JZA
Страница 2: ......
Страница 24: ...1 3 Component Names This Page Intentionally Blank 22 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 52: ...3 12 Wiring Checklist This Page Intentionally Blank 50 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 70: ...4 9 Test Run Checklist This Page Intentionally Blank 68 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 162: ...8 5 Communication Options This Page Intentionally Blank 160 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 210: ...C 13 Self Diagnostics This Page Intentionally Blank 208 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 230: ...Index This Page Intentionally Blank 228 SIEP C710606 33A OYMC AC Drive J1000 User Manual...
Страница 231: ...This Page Intentionally Blank SIEP C710606 33A OYMC AC Drive J1000 User Manual 229...