6. Measurement Device Setup and Connection
6-3
●
Wire & Connection Device
Power cable (100 VAC), RS-485 communications port cable, LAN cable, switching hub
USB cable (for KM1/KE1, A-miniB)
USB cable (for WZ series, accessory of WZ-MLAN01)
●
Computer for Setup Software
Install the setup software for each measurement device.
●
Documentation of Measurement Devices
User's Manual/Communications Manual for Measurement Devices
- The operation manual attached to a measurement device may not include necessary
information. Always refer to user's manual.
- For KM100 or KM20, see general catalog for energy-saving support devices (SGTE-616□).
- Refer to memory map on communications manual. It will help understanding of
measurement channels.
Measurement Device Setup
6.1.2.
This setup is required for a measurement device to connect to EQ100 and collect measured
data. As a result, measurement devices must be separately identified and configured.
For details of measurement device settings, see respective user's manual.
■
RS-485-Connected Measurement Device Settings
Select CompoWay/F protocol and configure the unit number and communications conditions.
Before doing so, define combinations of RS-485-connection measurement devices and four
RS-485 communications ports of EQ100. Configuration must be made so that the following
conditions for the RS-485 measurement devices to connect should be met for each RS-485
communications port.
- Communications settings (communication speed, data length, stop bits, vertical parity, and
protocol) must be the same
- Unit number of the measurement device to connect to one RS-485 communications port must
be unique (the number must not be used for other measurement device)
In addition, collect the configured setting details for each measurement device (e.g. unit number,
measurement type) to collect measured data from EQ100.
■
LAN-Connected Measurement Device Settings
Before configuration, define network setup for LAN and sub-LAN connection ports of EQ100.
Then define the following settings:
- Connection of LAN-connected measurement device and the LAN/sub-LAN connection port of
EQ100.
- Network setup of each measurement device (IP address, subnet mask)
The network setup for the LAN connection measurement device must be configured so as to
meet the following conditions:
- The host address must be unique (the same value must not be used for other LAN-connected
measurement device)
- The subnet mask value must correspond to the network address
In addition, collect the configured setting details for each measurement device (e.g. IP address,
measurement type) to collect measured data from EQ100.
■
Wireless Device Setup
A wireless device collects measured data via the wireless unit master (WZ-MLAN01).
Configuration of the wireless unit master is required. In case of a wireless device unit of
unidirectional communication, a combination of its group ID and the wireless unit ID is its
identifier.
Содержание EQ100-E
Страница 1: ...Sensor Network Server Model EQ100 E User s Manual Catalog No N196 E1 01H ...
Страница 55: ...2 Specifications 2 24 2 5 Dimensions Top View Front View Unit mm ...
Страница 92: ...7 EQ100 Settings 7 3 4 Click OK to view the EQ project setup menu Setting Menu ...
Страница 197: ...9 Web UI Function 9 24 3 In the Save As dialog box enter a destination to save and click Save Download is completed ...
Страница 255: ... MEMO ...