5. Installation and Wiring
5-6
5.5. Wiring Description
Power and Grounding Wires
5.5.1.
Precautions for
Correct Use
- Connect the power to the power terminals (L-terminal, N-terminal. Be sure to connect to the
correct terminal board.
■
AC Power
100 to 240 VAC power source must be supplied.
If one phase of the power source is grounded, the grounded phase must be connected to the N
terminal.
The power source must be within the following allowable power supply voltage range.
Supply Voltage
Allowable Power Supply Voltage Range
100 to 240 VAC
85 to 264 VAC
■
Grounding Wire
The grounding terminal must be class-D earthed (class-3 earthed in the older standards in
Japan).
■
Terminal Screw and Crimping Terminal
Terminal Screw
M3.5 captive screw
Recommended Tightening Torque
0.8 N
⋅
m
Recommended Crimping Terminal
(Unit: mm)
Precautions
- Use proper crimping terminals to the terminal block for wiring.
- Keep a little room upon wiring of power and grounding terminals. It should make easier the
dismounting task of EQ100 for battery replacement.
Electric shock may occur.
Before wiring on the terminal block and/or battery
replacement, turn off the power.
Otherwise the product may be damaged and/or disrupted.
The supply voltage must be within the specified range.
8.
0以
下
φ3.7
8.
0以
下
3
.7
<8
.0
<8
.0
CAUTION
AC Power
100 to 240V
Class D Grounding
(Class 3 Grounding)
Содержание EQ100-E
Страница 1: ...Sensor Network Server Model EQ100 E User s Manual Catalog No N196 E1 01H ...
Страница 55: ...2 Specifications 2 24 2 5 Dimensions Top View Front View Unit mm ...
Страница 92: ...7 EQ100 Settings 7 3 4 Click OK to view the EQ project setup menu Setting Menu ...
Страница 197: ...9 Web UI Function 9 24 3 In the Save As dialog box enter a destination to save and click Save Download is completed ...
Страница 255: ... MEMO ...