2. Specifications
2-22
Reference
- A measurement device that can log measured data by itself, e.g. KM100 and ZN-KMX21, logs
measured data with its internal clock. EQ100 collects measurement data using its internal
clock from measurement devices.
Collecting of measured data by a measurement device itself and EQ100 are separately
performed. The measured data of them may not be the same due to a difference between the
measurement timings.
■
Device Type and Maximum Measurement Channels
The maximum number of measurement channels of EQ100 is 500, including all measurement
devices and operation channels.
Under the limitation, shown below is a list of the maximum numbers of measurement channels
for measurement devices:
Connection
Method
Device
Type
Device Name
Maximum
Connections
Maximum Measurement
Channels
Collecting
Interval:
1 minute
Collecting
Interval:
5 minutes or
longer
RS-
485
RS-485-
Connected
Device
- Power Monitor
- Digital Panel Meter
- Temperature Controller
124 devices
(31 devices/
port x 4 ports)
160 channels
(40 channels/
port)
500 channels
(200 channels/
port)
LAN
LAN-
Connected
Device
- Portable Power Monitor
- Air Thermo Station
- Differential Pressure
Station
- Air Particle Sensor
- Power Station
- Air Flow Station
100 devices 500 channels 500 channels
Wireless
Device
Unit
- Wireless Unit Slave
(CompoWay/F)
30 devices
(*1)
(14 devices/
slave)
40 channels 120 channels
- Air Thermo Sensor
- Illumination Sensor
- Air Thermo Illumination
Sensor
- CO
2
Sensor
- Wireless Unit Slave
(Pulse Count)
30 devices
(*1)
Limitless in the channel
number (only the number of
devices to be connected is
limited)
PLC
- CJ Series
10 devices
500 channels 500 channels
Pulse Input
-
1 input
1 channel
1 channel
Operation
Channel
(A channel obtained by an
process operating a
measurement channel)
-
100 channels 100 channels
*1: The number of wireless device units is counted as the number of the slave units, regardless
of the number of LAN-connected master units and relay units.
Содержание EQ100-E
Страница 1: ...Sensor Network Server Model EQ100 E User s Manual Catalog No N196 E1 01H ...
Страница 55: ...2 Specifications 2 24 2 5 Dimensions Top View Front View Unit mm ...
Страница 92: ...7 EQ100 Settings 7 3 4 Click OK to view the EQ project setup menu Setting Menu ...
Страница 197: ...9 Web UI Function 9 24 3 In the Save As dialog box enter a destination to save and click Save Download is completed ...
Страница 255: ... MEMO ...