2. Specifications
2-16
Software Specifications
2.2.2.
Item
Details
Operation
Mode
Normal Mode
There are following three modes when operated normally:
Setup
Status
A status to configure the EQ100, register a
measurement device, and perform
communication test.
Collecting
Status
A status to collect and monitor energy data.
Under the collecting status, the setup cannot
be changed.
System
Error
Status
A status under which an instrument failure
occurred and no operation is available for the
setup and collecting statuses.
Safe Mode
A mode to recover from disaster or perform device
maintenance.
Data
Collecting
Function
Target Device
Communications
Path for Collecting
There are following two communications path for data
collecting:
- RS-485 communications (communications protocol:
CompoWay/F)
×
4
- LAN communications
×
2
Maximum
Measurement
Channels
Up to 500 channels (with limitations based on
measurement device type and collecting interval)
Collecting Interval
1 min/5 min/10 min/30 min/60 min
Pulse Input
Function
The number of pulses inputted during the collecting
interval is counted and saved to the pulse (input) channel.
Based on the pulse input count channel, its unit is
converted to an engineering unit (mainly energy unit) by
created operation expression.
Logging
Function
Target data, logging
interval, stored
memory
The following two data types are logged:
- Collected Data
Data collected from a measurement device is saved into
the internal memory.
- Event Log
Logs of EQ100 monitoring alarm, device alarm, and
internal events are saved into the internal memory as an
event log.
How to Start Saving
into Internal Memory
Any of the following operations starts collecting and saving
of the log when the status transfers from the setup to
collecting:
- Operation of collecting start on the Web UI screen
- Operation of logging start on EQ-Manager
- Pressing RUN/STOP button on the EQ100 front end
Setup
Function
EQ100 Setting
An EQ project is loaded that is created by EQ-Manager.
An EQ project is loaded by any of the following operations:
- Setup write function of EQ-Manager to write the EQ
project from a computer to EQ100.
- To attach an SD card containing an EQ project file to
EQ100 and write the EQ project.
- Web UI operation to write the EQ project from a
computer to EQ100.
Time
Synchronization
Synchronization with
EQ Server
Synchronizes the time with EQ server.
Synchronization with Synchronizes the time with SNTP server.
Содержание EQ100-E
Страница 1: ...Sensor Network Server Model EQ100 E User s Manual Catalog No N196 E1 01H ...
Страница 55: ...2 Specifications 2 24 2 5 Dimensions Top View Front View Unit mm ...
Страница 92: ...7 EQ100 Settings 7 3 4 Click OK to view the EQ project setup menu Setting Menu ...
Страница 197: ...9 Web UI Function 9 24 3 In the Save As dialog box enter a destination to save and click Save Download is completed ...
Страница 255: ... MEMO ...