206
Monitoring Functions
Section 7-1
7-1-3
Monitoring Parameters
Description
The I/O status of an NE1A-series or NE0A-series Controller or DST1-series
Safety I/O Terminal can be monitored using the Network Configurator. If the
configuration fails or if an error occurs in any I/O, monitoring this information
enables the user to determine the cause of the error.
Monitoring Using the Network Configurator
The user can monitor the parameters using any of the following methods:
1.
Select a device and select
Device
–
Monitor
from the menu bar. Click the
Parameters
Tab in the displayed window.
2.
Select a device and click the
Monitor Device
Button on the toolbar. Click
the
Parameters
Tab in the displayed window.
3.
Right-click a device and select
Monitor
from the pop-up menu. Click the
Parameters
Tab in the displayed window.
Содержание DeviceNet Safety
Страница 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Страница 6: ...iv...
Страница 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Страница 12: ......
Страница 14: ...xii...
Страница 18: ...xvi...
Страница 68: ......
Страница 98: ...64 Creating a Virtual Network Section 3 4 A new connected network will be created as shown below...
Страница 122: ......
Страница 167: ...133 Safety Slave Settings Section 5 2...
Страница 234: ......
Страница 266: ......
Страница 366: ......
Страница 372: ......
Страница 374: ......
Страница 375: ......