![Omron DeviceNet Safety Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/omron/devicenet-safety/devicenet-safety_system-configuration-manual_743566022.webp)
xx
Safety Precautions
3
3
Safety Precautions
!
WARNING
Safety functions may be impaired and serious injury may occasionally occur.
Do not use the test outputs of the products as safety outputs.
Safety functions may be impaired and serious injury may occasionally occur.
Do not use DeviceNet standard I/O data or explicit message data as safety sig-
nals.
Safety functions may be impaired and serious injury may occasionally occur.
Do not use the indicators on the products for safety operations.
Serious injury may possibly occur due to breakdown of safety outputs or test
outputs. Do not connect loads beyond the rated value to the safety outputs or
test outputs.
Safety functions may be impaired and serious injury may occasionally occur.
Wire the output lines and 24-VDC line so that they will not touch each other to
prevent a load from turning ON due to a short-circuit with the 24-VDC line.
Safety functions may be impaired and serious injury may occasionally occur.
Ground the 0-V side of the external power supply to prevent an output from turn-
ing ON due to a ground fault in a safety output or test output.
Safety functions may be impaired, and serious injury may occasionally occur.
Before connecting a device to the network, clear the previous configuration
data.
Safety functions may be impaired and serious injury may occasionally occur.
Before connecting a device to the network, configure the appropriate node
address and the baud rate.
Safety functions may be impaired and serious injury may occasionally occur.
Before operating the system, conduct user testing to confirm if the configura-
tion data of all the devices and their operations are correct.
Safety functions may be impaired, and serious injury may occasionally occur.
When replacing a device, confirm that the replacement device is appropriately
configured and operates properly.
Serious injury may possibly occur due to loss of required safety functions. Use
appropriate components or devices according to the requirements given in the
following table.
Control device
Requirements
Emergency stop switch
Use approved devices with a direct opening mechanism compliant with IEC/
EN 60947-5-1.
Door interlocking switch or
limit switch
Use approved devices with a direct opening mechanism compliant with IEC/
EN 60947-5-1 and capable of switching micro-loads of 4 mA at 24 VDC.
Safety sensor
Use approved devices compliant with the relevant product standards, regula-
tions, and rules in the country where they are used.
Relay with forcibly guided
contacts
Use approved devices with forcibly guided contacts compliant with EN
50205. For feedback, use devices with contacts capable of switching micro-
loads of 4 mA at 24 VDC.
Содержание DeviceNet Safety
Страница 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Страница 6: ...iv...
Страница 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Страница 12: ......
Страница 14: ...xii...
Страница 18: ...xvi...
Страница 68: ......
Страница 98: ...64 Creating a Virtual Network Section 3 4 A new connected network will be created as shown below...
Страница 122: ......
Страница 167: ...133 Safety Slave Settings Section 5 2...
Страница 234: ......
Страница 266: ......
Страница 366: ......
Страница 372: ......
Страница 374: ......
Страница 375: ......