63
Example Function Blocks for Data Exchange
Section 3-2
Step 1: Creating the Main Function Block
First create the main function block, which is the heart of the control system.
This example requires a Basic PID block (Block Model 011) and a First-order
Lag block (Block Model 141).
The following diagram shows the main function block.
Note
Set ITEM 024 (Set point setting mode) of the Basic PID block to 1 (Remote/
Local). The Remote/Local setting mode must be enabled in order for the
Remote/Local setting to be made with a contact input.
PV
(Feedback from
the whole system)
Input from
Monitor Plus
Output to
Monitor Plus