58
Data Exchange Method
Section 3-1
3-1-4
Exchanging Contact Signal Data
In order to read/write the Loop Control Unit or Board’s contact signal data, the
Contact Distributor (Block Model 201) and Internal Switch (Block Model 209)
blocks must be registered as a set and the Contact Distributor (Block Model
201) must be connected to each function block’s contact ITEMs. Set the tags
for Monitor Plus in the Internal Switch (Block Model 209) block’s bits.
Setting Bits from Monitor
Plus
1,2,3...
1.
Connect the Contact Distributor (Block Model 201) as the destination for
the function block’s contact input ITEM that you want to set. At the same
time, input (connect) the Internal Switch (Block Model 209) from the Con-
tact Distributor (Block Model 201).
2.
Set the tags for Monitor Plus in the Internal Switch (Block Model 209). Set
a tag name for each ITEM (S1 to S8).
Monitor Plus
Loop Control Unit or Board
Internal
Switch
(Block
Model 209)
Set tags for Monitor Plus.
(Select
Set
"to write data.)
Function
block
Function
block
Specify the tags
for Monitor Plus
and write data.
CPU Unit
Contact
Distributor
(Block
Model 201)
I/O memory
Contact
Contact
Contact
Contact
Write
Select
Setting.
Содержание CX-Process Monitor Plus 2
Страница 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Страница 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi Application Precautions 4...
Страница 41: ...26 Basic Operating Procedure Section 1 2...
Страница 243: ...228 Checking Configurations Section 5 7...
Страница 244: ...229 SECTION 6 Troubleshooting This section describes errors that can occur while using the CX Process Monitor Plus...
Страница 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Страница 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...