124
Annunciator Screens
Section 4-13
4-13 Annunciator Screens
Annunciator Screens display comprehensively the contacts status (mainly the
alarm status). To display the Annunciator Screen, click the
Annunciator
Screen
icon on the Overview Screen.
There are no particular limits to contacts that can be specified. Basically, how-
ever, register contacts that display the alarm status of the Control Block’s HH
(High/High Alarm), H (High Alarm), L (Low Alarm), and LL (Low/Low Alarm),
etc.
If an alarm/error occurs, the icon color will change and a beep will sound. At
the same time, two rows of eight wide-size characters making a user-regis-
tered message can be displayed.
You can display a total of 16 separate elements per screen as 4 rows x 4 col-
umns, to a maximum of five screens.
Element
Function block or ITEM set as send source
Function block
Control Blocks: Basic PID (011), Advanced PID (012), Blended PID (Block Model 013), Batch Flow-
rate Capture (Block Model 014), Indication and Setting (031), Indication and Operation (032), Ratio
Setting (033), Indicator (034), 2-position ON/OFF (001), 3-position ON/OFF (002)
Operation Blocks: High/Low Alarm (111), Segment Program 2 (157), ON/OFF Value Manipulator
(221), Motor Manipulator (222), Reversible Motor Manipulator (223), Motor Opening Manipulator
(224), Timer (205), Counter (208)
The following for all function blocks:
Analog input signals (Input Selector (Block Model 162))
Analog output signals (Constant Generator (Block Model 166))
Contact input signals or contact output signals for all function blocks, or contact value parameters
(Contact Distributor (Block Model 201) + Internal Switch (Block Model 209))
Display
Analog values: Bar graphs, numerical values, tank level
Contacts: Indicators, pumps, valves, pipes
Setting
Analog values: Numerical values (using Constant Generator (Block Model 166))
Contacts: Switches (using Contact Distributor (Block Model 201) + Internal Switch (Block Model
209))
Switch screens using this button.
If an error occurs, the Error Display Panel
and Screen Switching Button will both flash.
Sets the error display panel to
checked status (lit) when an alarm
has occurred.
The display of the error display
panel will be reset if the alarm has
been cleared (contact OFF status).
Resets the error display panel
when an alarm has occurred.
Содержание CX-Process Monitor Plus 2
Страница 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Страница 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi Application Precautions 4...
Страница 41: ...26 Basic Operating Procedure Section 1 2...
Страница 243: ...228 Checking Configurations Section 5 7...
Страница 244: ...229 SECTION 6 Troubleshooting This section describes errors that can occur while using the CX Process Monitor Plus...
Страница 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Страница 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...