116
Segment Program 2 Screens
Section 4-11
Segment Program 2
Trend Files
When Segment Program 2 data collection starts (i.e., when S1, ITEM 013,
turns ON), Segment Program 2 trend files are automatically created in binary
format for each Segment Program 2 Monitor Screen.
File Names
Segment Program 2 trend files are saved under the following file name for
each date.
File name: Starting date - Starting time - Segment Program 2 Screen
name.157
Example:
Segment Program 2 Monitor Screen Maximum Save Time
When the maximum save time (3, 30, or 180 days) has elapsed for a Segment
Program 2 Monitor Screen, the Segment Program 2 trend file is no longer
updated.
If S1 (ITEM 013) for the Segment Program 2 Block is ON, a new Segment
Program 2 trend file is created and segment data collection is restarted.
Segment Program 2 Trend File Save Cycles
A Segment Program 2 trend file is added each time segment data collection is
started.
A setting can be made on the System Info Screen so that Segment Program 2
trend files created outside of the regular cycle are automatically deleted.
For details on the System Info Screen, refer to
5-6-9 CSV File Auto-save Set-
tings
.
Starting and Stopping CX-Process Monitor Plus Operation
When the CX-Process Monitor Plus is stopped (either by stopping all CX-Pro-
cess Monitor Plus modules or by turning OFF the computer), the segment
data collection is stopped even if S1 (ITEM 013) of the Segment Program 2
Block is ON.
When the CX-Process Monitor Plus is restarted, the data collection starts
again, but the data is collected in a new Segment Program 2 trend file.
An option in the CRT Builder Dialog Box option (Segment Program 2 Screen)
from the Builder Window can be selected to enable segment data to continue
to be collected in the Segment Program 2 trend file from when the CX-Pro-
cess Monitor Plus was stopped.
20061201
161510
Segment.157
Starting date
(YYYYMMDD)
Starting time
(HHMMSS)
Segment Program 2 Screen name
Select this option.
Содержание CX-Process Monitor Plus 2
Страница 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Страница 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi Application Precautions 4...
Страница 41: ...26 Basic Operating Procedure Section 1 2...
Страница 243: ...228 Checking Configurations Section 5 7...
Страница 244: ...229 SECTION 6 Troubleshooting This section describes errors that can occur while using the CX Process Monitor Plus...
Страница 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Страница 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...