240
Reading/Writing Function Block ITEMs
Appendix A
Indication and Setting (Block Model 031)
Note
Only optional tags can be set.
ITEM
type
ITEM
Tag ITEM
Data
description
Data
range
CX-Process Monitor screen (R:Read W:Write)
Over-
view
Screen
Control
Screens
Tuning
Screens
Trend
Screens
Batch
Trend
Screen
Segment
Program
2 Screen
(See
note.)
Graphic
Screens
Annun-
ciator
Screens
Alarm
Log
Screens
Contact
input
000
MT_ST
Stop block oper-
ation com-
mand(0: Cancel
stop, 1: Stop)
0 or 1
R
(Color)
R
(Color)
R/W
R
R
R
R
R
Analog
input
007
PV
PV input
–15.00 to
+115.00%
R
R
R
R
R
R
Parameter
008
HH_SP
High/high alarm
setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
009
H_SP
High alarm set-
ting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
010
L_SP
Low alarm set-
ting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
011
LL_ SP
Low/low alarm
setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
Contact
output
013
HH
High/high alarm
output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
014
H
High alarm out-
put
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
015
L
Low alarm output 0 or 1
R
(Color)
R
R
R
R
R
R
R
R
016
LL
Low/low alarm
output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
Contact
input
017
ALM_OFF
Alarm stop
switch
0: Alarm, 1: Stop
0 or 1
R
(Color)
R/W
R
R
R
R/W
R
Parameter
019
PV_ABN
PV error display
0: Normal, 1:
Error
0 or 1
R
R
R
R
R
R
R
023
SP
Local Set Point
setting
–15.00 to
+115.00%
W
W
W
024
CAS_SET
Set Point setting
mode
0 or 1
R/W
R
R
R
R
R
R
Contact
input/
parameter
026
R/L_SW
Remote/Local
switch
0 or 1
R/W
R
R
R
R/W
R
Analog
output
029
SP
Current Set Point
output
–15.00 to
+115.00%
R
R
R
R
R
R
Parameter
099
OP_MK
Label
0 to 15
R/W
R/W
R
R
R
R/W
Содержание CX-Process Monitor Plus 2
Страница 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Страница 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi Application Precautions 4...
Страница 41: ...26 Basic Operating Procedure Section 1 2...
Страница 243: ...228 Checking Configurations Section 5 7...
Страница 244: ...229 SECTION 6 Troubleshooting This section describes errors that can occur while using the CX Process Monitor Plus...
Страница 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Страница 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...