241
Reading/Writing Function Block ITEMs
Appendix A
Indication and Operation (Block Model 032)
Note
Only optional tags can be set.
ITEM
type
ITEM
Tag ITEM
Data
description
Data
range
CX-Process Monitor screen (R:Read W:Write)
Over-
view
Screen
Control
Screens
Tuning
Screens
Trend
Screens
Batch
Trend
Screen
Segment
Program
2 Screen
(See
note.)
Graphic
Screens
Annun-
ciator
Screens
Alarm
Log
Screens
Contact
input
000
MT_ST
Stop block opera-
tion command(0:
Cancel stop, 1:
Stop)
0 or 1
R
(Color)
R
(Color)
R/W
R
R
R
R
R
Analog
input
007
PV
PV input
–15.00 to
+115.00%
R
R
R
R
R
R/W
Parameter
008
HH_SP
High/high alarm
setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
009
H_SP
High alarm setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
010
L_SP
Low alarm setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
011
LL_ SP
Low/low alarm
setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
Contact
output
013
HH
High/high alarm
output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
014
H
High alarm output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
015
L
Low alarm output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
016
LL
Low/low alarm
output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
Contact
input
017
ALM_OFF
Alarm stop switch
0: Alarm, 1: Stop
0 or 1
R
(Color)
R/W
R
R
R
R/W
R
Parameter
019
PV_ABN
PV error display
0: Normal, 1:
Error
0 or 1
R
R
R
R
R
R
R
Parameter
076
MH_LMT
High MV limit
±
320.00%
R
R/W
R
R
R
R/W
077
ML_ LMT
Low MV limit
±
320.00%
R
R/W
R
R
R
R/W
078
MHA
MV upper limit
output value
1: Upper limit or
more
0: Less than
upper limit
0 or 1
R
R
R
R
R
R
R
079
MLA
MV lower limit out-
put value
1: Lower limit or
less
0: Greater than
lower limit
0 or 1
R
R
R
R
R
R
R
Analog
input
084
X1
Auto input
±
320.00%
R
R
R
R
R
R
Contact
input
086
A/M_SW
Auto/Manual
switch
0: Manual, 1: Auto
0 or 1
R/W
R/W
R
R
R
R/W
R
Parameter
089
MV
Inversion of host
display of MV
±
320.00%
R/W
R/W
R
R
R
R/W
091
MV_ ABN
MV execution
error display
0: Normal, 1:
Error
0 or 1
R
R
R
R
R
R
R
R
098
MV_ IDX
MV index position
–15.00 to
+115.00%
R
R/W
R
R
R
R/W
099
OP_MK
Label
0 to 15
R/W
R/W
R
R
R
R/W
Содержание CX-Process Monitor Plus 2
Страница 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Страница 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi Application Precautions 4...
Страница 41: ...26 Basic Operating Procedure Section 1 2...
Страница 243: ...228 Checking Configurations Section 5 7...
Страница 244: ...229 SECTION 6 Troubleshooting This section describes errors that can occur while using the CX Process Monitor Plus...
Страница 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Страница 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...