24
Basic Operating Procedure
Section 1-2
• CSV tags:
Settings – Tag Setting – CSV Tag
• Tags for Monitor Plus:
Settings – Tag Setting – Monitor Plus Tag
d.
Generate the tag file for Monitor Plus:
Execute – Create Tag File –
Monitor Plus Tag
e.
Download the function block data to the Loop Control Unit/Board.
f.
Compile the monitor tags. Start the CX-Process Monitor Plus and click
the
Setup
Button.
g.
Enter password.
Note
(a) If the above steps are not performed using CX-Process Tool, you
cannot monitor using CX-Process Monitor Plus.
(b) The network address, node address, and unit address settings
made with CX-Process Tool are also used by the CX-Process
Monitor Plus.
3.
Configure the Screen Using CX-Process Monitor Plus. (Refer to
Section 4
Screen Configuration.
)
• Design the monitor system using CX-Process Monitor Plus.
• Create and register the Control screens, Trend screens, Graphic screens,
and Annunciator screens on Overview screens.
• When registering, specify on the screen the Loop Control Unit/Board data
by selecting the tags (CSV tags and tags for Monitor Plus) set using CX-
Process Tool.
• Set the communications conditions with the PLC using the system moni-
tor setting window (if using serial communications).
Perform the following procedure.
a.
Select
Omron
–
CX-Process Monitor Plus
–
CX-Process Monitor
Plus
from the Windows Start Menu.
b.
Click the
Setup
Button in the Main Window.
c.
Enter password.
d.
Click the
System Monitor Builder
Button
in the Setup Dialog Box,
and make settings using the System Monitor Setting Window.
e.
Click the
Graphic Builder
Button in the Setup Dialog Box, create the
Graphic Screen Create Window (including tag name specifications),
and save.
f.
Click the
CRT Builder
Button in the Setup Dialog Box, and register the
screen using the Builder Window (including Tag name specifications).
g.
From the Builder Window
Settings
menu, select
Save
, and then click
the
OK
Button.
4.
Check Screen Configuration Using CX-Process Monitor Plus. (Refer to
5-
7 Checking Configurations.
)
• Check if you can monitor the Loop Control Unit/Board using the config-
ured screen.
• Start FinsGateway Serial Unit communications according to the commu-
nications conditions set using the System monitor setting window by start-
ing the monitoring process (i.e., start FinsGateway Controller Link and
Ethernet manually).
Perform the following operation.
a.
Click the
Setup
Button in the Main Window.
b.
Enter password.
Содержание CX-Process Monitor Plus 2
Страница 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Страница 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi Application Precautions 4...
Страница 41: ...26 Basic Operating Procedure Section 1 2...
Страница 243: ...228 Checking Configurations Section 5 7...
Страница 244: ...229 SECTION 6 Troubleshooting This section describes errors that can occur while using the CX Process Monitor Plus...
Страница 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Страница 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...