104
Batch Trend Screens
Section 4-10
4-10-2 Collecting and Saving Trend Data
Triggers for Starting
and Ending Trend
Data Collection
There are two ways of starting and ending trend data collection, as described
below.
Trigger Tags
Trigger tags can be used to start and end trend data collection according to
the status of the specified tags.
Set the tags as follows, depending on the type of tag data (contact ITEM or
analog ITEM):
Contact ITEM: Data collection starts and ends according to the ON and
OFF status.
Analog ITEM: Data collection starts when the tag value is equal to or
greater than the batch start value that has been set, and it
ends when the tag value is less than the batch stop value.
Batch Trend Screen Operations
Trend data collection can be started and stopped at any time from the Batch
Trend Screen.
Use the following procedure to start trend data collection.
1,2,3...
1.
Click the collection status display area in the Batch Trend Screen.
2.
The Batch Collection Status Dialog Box will be displayed.
Click the
Batch start request
Button. (If a trigger tag is set, a batch stop
request can be executed. Even if it is ended, however, data collection will
immediately start when the data collection conditions are satisfied.
Use this operation in cases such as switching to another batch when the
collection conditions are already satisfied.)
Click here.
Starts trend data collection.
Stops trend data collection.
Содержание CX-Process Monitor Plus 2
Страница 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Страница 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi Application Precautions 4...
Страница 41: ...26 Basic Operating Procedure Section 1 2...
Страница 243: ...228 Checking Configurations Section 5 7...
Страница 244: ...229 SECTION 6 Troubleshooting This section describes errors that can occur while using the CX Process Monitor Plus...
Страница 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Страница 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...