302
Inverter Positioning
Section 5-3
PLC Setup
■
Serial Port Communications Settings
Note
(1) Set the baud rate and parity check settings to the same value as for the
Inverter communications parameters.
(2) Set the serial port to the serial gateway communications mode.
n153
RS-422A/485 communications
Slave address
Setting range: 0 to 32
00: Communications disabled
01 to 32: Slave address
0
1
n154
RS-422A/485 baud rate selec-
tion
0: 2,400 bps
1: 4,800 bps
2: 9,600 bps
3: 19,200 bps
2
2
n155
RS-422A/485 parity selection
0: Even
1: Odd
2: No parity
0
0
n156
RS-422A/485 send wait time
Set value: 10 to 65 ms
Setting unit: 1 ms
10 ms
10 ms
n157
RS-422A/485 RTS control
selection
0: RTS control enabled
1: RTS control disabled
0
0
Parameter
No.
Name
Description
Default
Setting
Содержание CP1L-L14D Series
Страница 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Страница 523: ...490 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...498 Replacing User serviceable Parts Section 10 2...
Страница 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...636 Index...
Страница 671: ...638 Revision History...