92
Installation Precautions
Section 3-2
Accessibility for
Operation and
Maintenance
• To ensure safe access for operation and maintenance, separate the PLC
as much as possible from high-voltage equipment and moving machinery.
• The PLC will be easiest to install and operate if it is mounted at a height of
about 1,000 to 1,600 mm.
!Caution
Do not touch the power supply or the area around the I/O terminals while
power is being supplied or immediately after power has been turned OFF.
Doing so may result in burns.
!Caution
After the power supply has been turned OFF, wait until the PLC has suffi-
ciently cooled before touching it.
Improving Noise
Resistance
• Do not mount the PLC in a control panel containing high-voltage equip-
ment.
• Install the PLC at least 200 mm from power lines.
• Ground the mounting plate between the PLC and the mounting surface.
Mounting in a Panel
• The CP1L must be installed in the orientation shown below to ensure ade-
quate cooling.
SYSMAC CP1L
200 mm min.
200 mm
min.
Power lines
Содержание CP1L-L14D Series
Страница 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Страница 523: ...490 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...498 Replacing User serviceable Parts Section 10 2...
Страница 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...636 Index...
Страница 671: ...638 Revision History...