Wiring CP1L CPU Units
Section 3-4
Noise from External
Wiring
Take the following points into account when externally wiring I/O, power sup-
ply, and power lines.
• When multi-conductor signal cable is being used, avoid combining I/O
wires and other control wires in the same cable.
• If wiring racks are parallel, allow at least 300 mm between them.
• If the I/O wiring and power cables must be placed in the same duct, they
must be shielded from each other using grounded steel sheet metal.
Surge Suppressor Specifications
Resistance: 50
Ω
Capacitance: 0.47
µ
F
Voltage: 200
V
Diode Specifications
Breakdown voltage:
3 times load voltage min.
Mean rectification current: 1 A
300 mm min.
300 mm min.
PLC I/O wiring
PLC power supply
cable and general
control circuit wiring
Power lines
Low-current cables
Control cables
Power cables
Ground to 100
Ω
or less
200 mm min.
PLC I/O wiring
PLC power
supply cable
and general
control circuit
wiring
Power lines
Steel sheet metal
Ground to 100
Ω
or less
Содержание CP1L-L14D Series
Страница 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Страница 523: ...490 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...498 Replacing User serviceable Parts Section 10 2...
Страница 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...636 Index...
Страница 671: ...638 Revision History...