511
Auxiliary Area Allocations by Function
Appendix C
Inverter Positioning
Inverter Positioning 0 and 1
Pulse Output, Output
Stopped Error Flag
ON when an error occurred while outputting pulses in the
pulse output 0 origin search function.
OFF: No error
ON: Stop error occurred.
Read-only
• Cleared when power is turned
ON.
• Updated when origin search
starts.
• Updated when a pulse output
stop error occurs.
PWM Output, Output
In-progress Flag
ON when pulses are being output from the PWM output.
OFF: Stopped
ON: Outputting pulses.
Read-only
• Cleared when power is turned
ON.
• Cleared when operation starts or
stops.
• Updated when pulse output
starts or stops.
Pulse Output Stop
Error Code
If a Pulse Output Stop Error occurs, the error code is writ-
ten to this word.
Read-only
• Cleared when power is turned
ON.
• Updated when origin search
starts.
• Updated when a pulse output
stop error occurs.
Pulse Output Reset Bit
The pulse output PV will be cleared when this bit is turned
ON.
Read/Write
Cleared when power is turned
ON.
Pulse Output CW Limit
Input Signal Flag
This is the CW limit input signal for the pulse output, which
is used in the origin search. To use this signal, write the
input from the actual sensor as an input condition in the lad-
der program and output the result to this flag.
Read/Write
Cleared when power is turned
ON.
Pulse Output CCW
Limit Input Signal Flag
This is the CCW limit input signal for the pulse output,
which is used in the origin search. To use this signal, write
the input from the actual sensor as an input condition in the
ladder program and output the result to this flag.
Read/Write
Cleared when power is turned
ON.
Pulse Output Position-
ing Completed Signal
This is the positioning completed input signal used in the
origin search for the pulse output. The input signal from the
servo driver is output to this bit from the ladder program to
enable using the signal.
Read/Write
Cleared when power is turned
ON.
Item
Inverter
positioning 0
Inverter
positioning 1
Inverter Frequency Command Value
A23
A33
Present Value of Unsigned Output
Value
Leftmost 4 digits
A21
A31
Rightmost 4 digits
A20
A30
Present Value of Signed Output
Value
Leftmost 4 digits
A25
A35
Rightmost 4 digits
A24
A34
Operation Command Flag
A26.00
A36.00
Forward Operation Command Flag
A26.01
A36.01
Reverse Operation Command Flag
A26.02
A36.02
In-position Flag
A26.03
A36.03
Error Counter Error Flag
A26.04
A36.04
Error Counter Pulse Output Flag
A26.05
A36.05
Error Counter Pulse Output Acceleration/Deceleration Flag A26.06
A36.06
Error Counter Alarm Flag
A26.07
A36.07
Inverter Positioning Output Value Sign Flag
A26.15
A36.15
Error Counter Present Value, Signed
A22
A32
Present Value of Pulse Output to
Inverter, Relative Value
Leftmost 4 digits
A29
A39
Rightmost 4 digits
A28
A38
Error Counter Reset Bit
A562.00
A563.00
Error Counter Disable Bit
A562.01
A563.01
Present Value of High-speed
Counter
Leftmost 4 digits
A271
A273
Rightmost 4 digits
A270
A272
Present Value of Internal Pulse Out-
put
Leftmost 4 digits
A271
A279
Rightmost 4 digits
A270
A278
Name
Description
Read/Write
Updated
Содержание CP1L - 12-2007
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 428: ...395 Clock Section 6 9...
Страница 429: ...396 Clock Section 6 9...
Страница 523: ...488 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...496 Replacing User serviceable Parts Section 10 2...
Страница 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...634 Index...
Страница 671: ...636 Revision History...