240
Pulse Outputs
Section 5-2
6.
When the stocker is full, it is moved (CIO 100.02) and only the conveyor is
lowered (absolute positioning) when stoker movement is completed (CIO
0.04).
The operation can be canceled and pulse output stopped at any point using
the Emergency Switch Input (CIO 0.01).
Preparation
■
PLC Setup
Note
The origin search enable setting is read when the power supply is turned ON.
DM Area Settings
Settings for PLS2(887) for Fixed-distance Positioning (D0 to D7)
Settings for PLS2(887) to Return to Start (D10 to D17)
Setting details
Enable origin search function for pulse output 0.
Setting details
Address
Data
Acceleration rate: 1,000 Hz/4 ms
D0
03E8
Deceleration rate: 1,000 Hz/4 ms
D1
03E8
Target frequency: 50,000 Hz
D2
C350
D3
0000
Number of output pulses: 10,000 pulses
D4
2710
D5
0000
Starting frequency: 0 Hz
D6
0000
D7
0000
Setting details
Address
Data
Acceleration rate: 300 Hz/4 ms
D10
012C
Deceleration rate: 200 Hz/4 ms
D11
00C8
Target frequency: 50,000 Hz
D12
C350
D13
0000
Содержание CP1L - 12-2007
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 428: ...395 Clock Section 6 9...
Страница 429: ...396 Clock Section 6 9...
Страница 523: ...488 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...496 Replacing User serviceable Parts Section 10 2...
Страница 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...634 Index...
Страница 671: ...636 Revision History...