509
Auxiliary Area Allocations by Function
Appendix C
Built-in Outputs
Pulse Outputs 0, 1
Name
Description
Read/Write
Updated
High-speed Counter PV
Contains the PV of the high-speed counter.
Read-only
• Cleared when power is turned ON.
• Cleared when operation starts.
• Updated each cycle during oversee-
ing process.
• Updated when PRV(881) instruction
is executed for the corresponding
counter.
High-speed
Counter Range
Comparison
Condition Met
Flags
Range 1
These flags indicate whether the PV is within the
specified ranges when the high-speed counter is
being operated in range-comparison mode.
OFF: PV not in range
ON: PV in range
Read-only
• Cleared when power is turned ON.
• Cleared when operation starts.
• Cleared when range comparison
table is registered.
• Updated each cycle during oversee-
ing process.
• Updated when PRV(881) instruction
is executed to read range compari-
son results.
Range 2
Range 3
Range 4
Range 5
Range 6
Range 7
Range 8
High-speed Counter Com-
parison In-progress Flag
This flag indicates whether a comparison operation
is being executed for the high-speed counter.
OFF: Stopped.
ON: Being executed.
Read-only
• Cleared when power is turned ON.
• Cleared when operation starts.
• Updated when comparison operation
starts or stops.
High-speed Counter Over-
flow/Underflow Flag
This flag indicates when an overflow or underflow
has occurred in the high-speed counter PV. (Used
with the linear mode counting range only.)
OFF: Normal
ON: Overflow or underflow
Read-only
• Cleared when power is turned ON.
• Cleared when operation starts.
• Cleared when the PV is changed.
• Updated when an overflow or under-
flow occurs.
High-speed Counter
Count Direction
This flag indicates whether the high-speed counter
is currently being incremented or decremented. The
counter PV for the current cycle is compared with
the PLC in last cycle to determine the direction.
OFF: Decrementing
ON: Incrementing
Read-only
• Setting used for high-speed counter,
valid during counter operation.
High-speed Counter
Reset Bit
When the reset method is set to Phase-Z
Software reset, the corresponding high-speed
counter's PV will be reset if the phase-Z signal is
received while this bit is ON.
When the reset method is set to a software reset,
the corresponding high-speed counter's PV will be
reset in the cycle when this bit goes ON.
Read/Write
• Cleared when power is turned ON.
High-speed Counter Gate
Bit
When a counter's Gate Bit is ON, the counter's PV
will not be changed even if pulse inputs are received
for the counter.
When the bit is turned OFF again, counting will
restart and the high-speed counter's PV will be
updated.
When the reset method is set to Phase-Z
Software reset, the Gate Bit is disabled while the
corresponding Reset Bit is ON.
Read/Write
• Cleared when power is turned ON.
Item
Pulse output
0
Pulse output
1
Pulse Output PV
Leftmost 4 digits
A277
A279
Rightmost 4 digits
A276
A278
Pulse Output Accel/Decel Flag
A280.00
A281.00
Pulse Output Overflow/Underflow Flag
A280.01
A281.01
Pulse Output, Output Amount Set Flag
A280.02
A281.02
Pulse Output, Output Completed Flag
A280.03
A281.03
Pulse Output, Output In-progress Flag
A280.04
A281.04
Pulse Output No-origin Flag
A280.05
A281.05
Pulse Output At-origin Flag
A280.06
A281.06
Pulse Output, Output Stopped Error Flag
A280.07
A281.07
PWM Output, Output In-progress Flag
A283.00
A283.08
Содержание CP1L - 12-2007
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 428: ...395 Clock Section 6 9...
Страница 429: ...396 Clock Section 6 9...
Страница 523: ...488 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...496 Replacing User serviceable Parts Section 10 2...
Страница 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...634 Index...
Страница 671: ...636 Revision History...