439
Temperature Sensor Units
Section 7-5
Note
Accuracy for a K-type sensor at
−
100
°
C or less is
±
4
°
C
±
1 digit max.
Using Temperature Sensor Units
Connecting Temperature
Sensor Units
A maximum of three CPM1A-TS002 and CPM1A-TS102 Temperature Sensor
Units can be connected, because each is allocated four words.
Setting Temperature Ranges
Note
(1) Always turn OFF the power supply before setting the temperature range.
(2) Never touch the DIP switch or rotary switch during Temperature Sensor
Unit operation. Static electricity may cause operating errors.
The Temperature Sensor Unit’s DIP switch and rotary switch are used to set
the temperature unit, to select 2-decimal-place Mode is to be used, and to set
the temperature input range.
Item
CP1W-TS001
CPM1A-TS001
CP1W-TS002
CPM1A-TS002
CP1W-TS101
CPM1A-TS101
CP1W-TS102
CPM1A-TS102
Temperature sensors
Thermocouples
Platinum resistance thermometer
Switchable between K and J, but same type
must be used for all inputs.
Switchable between Pt100 and JPt100, but
same type must be used for all inputs.
Number of inputs
2
4
2
4
Allocated input words
2
4
2
4
Accuracy
(The larger of
±
0.5% of converted value or
±
2
°
C)
±
1 digit max. (See note.)
(The larger of
±
0.5% of converted value or
±
1
°
C)
±
1 digit max.
Conversion time
250 ms for 2 or 4 input points
Converted temperature data
16-bit binary data (4-digit hexadecimal)
Isolation
Photocouplers between all temperature input signals
Current consumption
5 VDC: 40 mA max., 24 VDC: 59 mA max.
5 VDC: 54 mA max., 24 VDC: 73 mA max.
Connect the Unit.
Set the temperature ranges.
Connect the temperature
sensors.
Program operation in the
ladder program.
•
Connect the Temperature Sensor Unit.
•
Set the temperature unit, 2-decimal-place Mode
if required, and set the temperature input range.
•
Connect temperature sensors.
•
Read temperature data stored in the input word.
SYSMAC
CP1L
L1
L2/N
COM
01
03
05
07
09
11
01
03
05
07
09
11
00
02
04
06
08
10
00
02
04
06
08
10
00
01
02
03
04
06
00
01
03
04
06
COM
COM
COM
COM
05
07
COM
02
COM
05
07
IN
OUT
IN
00
C H
C H
02
04
06
08
10
OUT
01
C OM
03
05
07
09
11
C OM
CO M
C OM
03
CO M
06
00
01
02
04
05
07
00 01 02 03 04 05 06 07
08 09 10 11
20EDR1
C H
00 01 02 03 04 05 06 07
N C
N C
N C
C H
EXP
IN
00
02
01
C OM
03
C OM
05
07
04
06
C H 00 01 02 03
08 09 10 11
8ED
EXP
CP1L CPU Unit
CP1W-20EDR1/
CPM1A-20EDR1
Expansion I/O Unit
CP1W-8ED/
CPM1A-8ED
Expansion I/O Unit
CP1W-TS001/TS101/
CPM1A-TS001/TS101
Temperature Sensor Unit
Содержание CP1L - 12-2007
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 428: ...395 Clock Section 6 9...
Страница 429: ...396 Clock Section 6 9...
Страница 523: ...488 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...496 Replacing User serviceable Parts Section 10 2...
Страница 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...634 Index...
Страница 671: ...636 Revision History...