523
Auxiliary Area Allocations by Function
Appendix C
Communications
Networks
Network Communications Information
Information When Automatically Allocating Communications Ports
Serial Port 1 Information (CP1L CPU Units with M CPU Type)
Name
Address
Description
Access
Updated
Communications Port
Enabled Flags
A202.00 to
A202.07
ON when a network instruction or background execution
can be executed with the corresponding port number.
Bits 00 to 07 correspond to communications ports 0 to 7.
Read-only
Communications Port Com-
pletion Codes
A203 to
A210
These words contain the completion codes for the corre-
sponding port numbers when network instructions have
been executed.
Words A203 to A210 correspond to communications
ports 0 to 7.
Read-only
Communications Port Error
Flags
A219.00 to
A219.07
ON when an error occurred during execution of a net-
work instruction.
OFF when a normal response is returned.
Bits 00 to 07 correspond to communications ports 0 to 7.
Read-only
Name
Address
Description
Access
Updated
Network Communications
Port Allocation Enabled Flag
A202.15
ON when there is a communications port available for
automatic allocation.
Note
Use this flag to confirm whether a communica-
tions port is available for automatic allocation
before executing communications instructions
when using 9 or more communications instruc-
tions simultaneously.
Read-only
First Cycle Flags after Net-
work Communications Fin-
ished
A214.00 to
A214.07
Each flag will turn ON for just one cycle after communi-
cations have been completed. Bits 00 to 07 correspond
to ports 0 to 7. Use the Used Communications Port Num-
ber stored in A218 to determine which flag to access.
Note
These flags are not effective until the next cycle
after the communications instruction is executed.
Delay accessing them for at least one cycle.
Read-only
First Cycle Flags after Net-
work Communications Error
A215.00 to
A215.07
Each flag will turn ON for just one cycle after a communi-
cations error occurs. Bits 00 to 07 correspond to ports 0
to 7. Use the Used Communications Port Number stored
in A218 to determine which flag to access. Determine the
cause of the error according to the Communications Port
Completion Codes stored in A203 to A210.
Note
These flags are not effective until the next cycle
after the communications instruction is executed.
Delay accessing them for at least one cycle.
Read-only
Network Communications
Completion Code Storage
Address
A216 to
A217
The completion code for a communications instruction is
automatically stored at the address with the I/O memory
address given in these words.
Place this address into an index register and use indirect
addressing through the index register to read the com-
munications completion code.
Read-only
Used Communications Port
Numbers
A218
Stores the communications port numbers used when a
communications instruction is executed using automatic
communication port allocations.
0000 to 0007 hex: Communications port 0 to 7
Read-only
Name
Address
Description
Access
Updated
Peripheral Port Communica-
tions Error Flag
A392.12
ON when a communications error has occurred at the
serial port 1.
Read-only
Peripheral Port Restart Bit
A526.01
Turn this bit ON to restart the serial port 1.
Read/write
Peripheral Port Settings
Change Bit
A619.01
ON while the serial port 1’s communications settings are
being changed.
Read/write
Peripheral Port Error Flags
A528.08 to
A528.15
These flags indicate what kind of error has occurred at
the serial port 1.
Read/write
Serial Port 1 Send Ready
Flag
(No-protocol Mode)
A392.13
ON when the serial port 1 is able to send data in no-pro-
tocol mode.
Read-only
Содержание CP1L - 12-2007
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 428: ...395 Clock Section 6 9...
Страница 429: ...396 Clock Section 6 9...
Страница 523: ...488 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...496 Replacing User serviceable Parts Section 10 2...
Страница 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...634 Index...
Страница 671: ...636 Revision History...