299
Inverter Positioning
Section 5-3
Example settings of 3G3MV parameters are listed below. Refer to the
User’s
Manual
of the Inverter for details on the parameters.
Parameter
No.
Name
Description
Default
Setting
n003
RUN command selection
0: The RUN Key and STOP/RESET Key on the
Digital Operator are enabled.
1: Multi-function input is enabled through the con-
trol circuit terminals.
2: RS-422A/485 communications are enabled.
3: Input is enabled from the optional Communica-
tions Unit.
0
2
n004
Frequency reference selection
0: Frequency reference adjustment
1: Frequency reference 1 (n024)
2: Frequency reference control terminal (0 to 10
V)
3: Frequency reference control terminal (4 to 20
mA)
4: Frequency reference control terminal (0 to 20
mA)
5: Pulse train reference control terminal
6: Frequency reference through RS-422A/RS-485
7: Multi-function analog voltage input (0 to 10 V)
8: Multi-function analog current input (4 to 20 mA)
9: Frequency reference input through optional
Communications Unit.
0
6
n005
Stopping method selection
0: Decelerates to stop
1: Coasts to stop
0
0
n006
Reverse rotation-prohibit
selection
0: Reverse enabled
1: Reverse disabled
0
0
n011
Maximum frequency (FMAX)
50.0 to 400.0 Hz (0.1-Hz increments)
60.0 Hz
60.0 Hz
(Depends
on machine
configura-
tion.)
n016
Minimum output frequency
(FMIN)
0.1 Hz to 10.0 Hz (0.1-Hz increments)
1.5 Hz
0.1 Hz
n018
Acceleration/deceleration time
setting unit
0: 0.1 s
1: 0.01 s
0
0
n019
Acceleration time 1
0 to 6,000 s
10.0 s
0
n020
Deceleration time 1
0 to 6,000 s
10.0 s
0
n151
RS-422A/485 communications
timeover detection selection
(The time between receiving
PLC signals is monitored, Tim-
eout time: 2 s.)
0: Detects time-over, fatal error, and the Inverter
coasts to a stop.
1: Detects time-over, detects fatal error, and the
Inverter decelerates to a stop in deceleration time
1.
2: Detects time-over, detects fatal error, and the
Inverter decelerates to a stop in deceleration time
2.
3: Detects time-over, detects nonfatal error warn-
ing, and the Inverter continues operating.
4: No time-over is detected.
0
0
n152
RS-422A/485 communications
frequency reference/display
unit selection
0: 0.1 Hz
1: 0.01 Hz
2: Converted value based on 30,000 decimal as
maximum frequency
3: 0.1% (Maximum frequency: 100%)
0
1
Содержание CP1L - 12-2007
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 428: ...395 Clock Section 6 9...
Страница 429: ...396 Clock Section 6 9...
Страница 523: ...488 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...496 Replacing User serviceable Parts Section 10 2...
Страница 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...634 Index...
Страница 671: ...636 Revision History...