341
Quick-response Inputs
Section 6-2
Interrupt Input and
Quick-response Input
Specifications
Procedure
Restrictions
Inputs cannot be used as quick-response inputs when they are being used as
general-purpose (normal) inputs, input interrupts, or high-speed counter
inputs.
Item
Specification
ON delay
30
µ
s max.
OFF delay
150
µ
s max.
Response pulse
ON
OFF
30
µ
s min.
150
µ
s min.
Select quick-response inputs.
Wire inputs.
PLC Setup settings
•
When IN0 to IN5 are used as quick response inputs,
set the corresponding built-in input's Interrupt Input
setting to Quick in the PLC Setup's Built-in Input Tab.
•
Use the quick-response inputs in
instructions such as LD.
Ladder program